Installation manual

Configuration Mode (ConF)
120 S1A28692 03/2010
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
AI1-
[AI1 CONFIGURATION]
AI1A [AI1 assignment]
nO
AO1
Fr1
Fr2
SA2
PIF
tAA
dA2
PIM
FPI
SA3
Fr1b
dA3
FLOC
MA2
MA3
PES
IA01
...
IA10
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI1 in order to check, for example, for compatibility problems.
[No] (nO): Not assigned
[AO1 assignment] (AO1): Analog output AO1
[Ref.1 channel] (Fr1): Reference source 1
[Ref.2 channel] (Fr2): Reference source 2
[Summing ref. 2] (SA2): Summing reference 2
[PID feedback] (PIF): PI feedback (PI control)
[Torque limitation] (tAA): Torque limitation: Activation by an analog value
[Subtract. ref. 2] (dA2): Subtracting reference 2
[Manual PID ref.] (PIM): Manual speed reference of the PI(D) regulator (auto-man)
[PID speed ref.] (FPI): Speed reference of the PI(D) regulator (predictive reference)
[Summing ref. 3] (SA3): Summing reference 3
[Ref.1B channel] (Fr1b): Reference source 1B
[Subtract. ref. 3] (dA3): Subtracting reference 3
[Forced local] (FLOC): Forced local reference source
[Ref.2 multiplier] (MA2): Multiplying reference 2
[Ref. 3 multiplier] (MA3): Multiplying reference 3
[Weight input]
(PES): Hoisting: Exter
nal weight measurement function
[IA01] (IA01): Function blocks: Analog Input 01
...
[IA10] (IA10): Function blocks: Analog Input 10
AI1t [AI1 Type]
[Voltage] (10U)
10U [Voltage] (10U): Positive voltage input (negative values are interpreted as zero: the input is unidirectional)
UIL1 [AI1 min value]
0 to 10.0 V 0 V
AI1 voltage scaling parameter of 0%.
UIH1 [AI1 max value]
0 to 10.0 V 10.0 V
AI1 voltage scaling parameter of 100%.
AI1F [AI1 filter]
0 to 10.00 s 0 s
Interference filtering.
AI1L [AI1 range]
[0 - 100%] (POS)
POS
nEG
[0 - 100%] (POS): Positive logical
[+/- 100%] (POS): Positive and negative logical
AI1E [AI1 Interm. point X]
0 to 100% 0%
Input delinearization point coordinate. Percentage of the physical input signal.
0% corresponds to [AI1 min value] (UIL1).
100% corresponds to [AI1 max value] (UIH1).
AI1S [AI1 Interm. point Y]
0 to 100% 0%
Output delinearization point coordinate (frequency reference).
Percentage of the internal frequency reference corresponding to the [AI1 Interm. point X] (A11E) percentage of physical
input signal.
I_O- [INPUTS / OUTPUTS CFG] (continued)
AI2- [AI2 CONFIGURATION]
AI2A [AI2 assignment]
Identical to [AI1 assignment] (A11A) page 120.
AI2t [AI2 Type]
[Voltage +/-] (n10U)
10U [Voltage] (10U): 0 - 10 V
UIL2 [AI2 min value]
0 to 10.0 V 0 V
AI2 voltage scaling parameter of 0%.
DRI- > CONF > FULL > I_O- > AI1-