Use of analog output AO1 as a logic output
Analog output AO1 can be used as a logic output, by assigning DO1. In this case, when set to 0, this output
corresponds to the AO1 min. value (0 V, or 0 mA for example), and when set to 1 to the AO1 max. value (10
V, or 20 mA for example).
The electrical characteristics of this analog output remain unchanged. As these characteristics are different
from logic output characteristics, check that it is still compatible with the intended application.
(1) 0 to 9,999 ms then 10.00 to 60.00 s on the integrated display terminal.
Code Name / Description Adjustment range Factory setting
I_O- [INPUTS / OUTPUTS CFG] (continued)
dO1- [DO1 CONFIGURATION]
dO1 [DO1 assignment]
[No] (nO)
bLC
LLC
OCC
EbO
tSY
dCO
OL01
...
OL10
Identical to [R1 Assignment] (r1) page 123
with the addition of (shown for information only as these selections can only be
configured in the [APPLICATION FUNCT.] (FUn-)) menu:
[Brk control] (bLC): Brake contactor control
[Input cont.] (LLC): Line contactor control
[Output cont] (OCC): Output contactor control
[End reel] (EbO): End of reel(traverse control function)
[Sync. wobble] (tSY): "Counter wobble" synchronization
[DC charging] (dCO): DC bus precharging contactor control
[OL01] (OL01): Function blocks: Logical Output 01
...
[OL10] (OL10): Function blocks: Logical Output 10
dO1d [DO1 delay time]
0 to 60,000 ms (1) 0 ms
The delay cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [Output cont.] (OCC) and [Input cont.] (LLC)
assignments, and remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information becomes true.
dO1S [DO1 active at]
[1 ] (POS)
POS
nEG
Configuration of the operating logic:
[1] (POS): State 1 when the information is true
[0] (nEG): State 0 when the information is true
The configuration [1 ] (POS) cannot be modified for the [No drive flt] (FLt), [Brk control] (bLC) and [Input cont.] (LLC)
assignments.
dO1H [DO1 holding time]
0 to 9,999 ms 0 ms
The holding time cannot be set for the [No drive flt] (FLt), [Brk control] (bLC) and [Input cont] (LLC) assignments, and
remains at 0.
The change in state only takes effect once the configured time has elapsed, when the information becomes false.
DRI- > CONF > FULL > I_O- > DO1-