Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 129
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
I_O- [INPUTS / OUTPUTS CFG] (continued)
AO1- [AO1 CONFIGURATION]
AO1 [AO1 assignment]
[No] (nO)
nO
OCr
OFr
OFS
OrP
trq
Stq
OrS
OPS
OPF
OPE
OPI
OPr
UOP
tHr
tHr2
tHr3
tHd
tqL
d01
tqMS
OA01
...
OA10
[No] (nO): Not assigned
[I motor] (OCr): Current in the motor, between 0 and 2 In (In = rated drive current indicated in the Installation manual and on
the drive nameplate)
[Motor freq.] (OFr): Output frequency, from 0 to [Max frequency] (tFr)
[Sig. o/p frq.] (OFS): Signed output frequency, between - [Max frequency] (tFr) and + [Max frequency] (tFr)
[Ramp out.] (OrP): From 0 to [Max frequency] (tFr)
[Motor torq.] (trq): Motor torque, between 0 and 3 times the rated motor torque
[Sign. torque] (Stq): Signed motor torque, between -3 and +3 times the rated motor torque. The + sign corresponds to the
motor mode and the - sign to the generator mode (braking).
[sign ramp] (OrS): Signed ramp output, between - [Max frequency] (tFr) and + [Max frequency] (tFr).
[PID ref.]
(OPS): PID
regulator reference between [Min PID reference] (PIP1) and [Max PID reference] (PIP2).
[PID feedbk] (OPF): PID regulator feedback between [Min PID feedback] (PIF1) and [Max PID feedback] (PIF2)
[PID error] (OPE): PID regulator error between- 5 % and + 5 % of ([Max PID feedback] (PIF2) - [Min PID feedback]
(PIF1))
[PID output] (OPI): PID regulator output between [Low speed] (LSP) and [High speed] (HSP)
[Mot. power] (OPr): Motor power, between 0 and 2.5 times [Rated motor power] (nPr)
[Motor volt.] (UOP): Voltage applied to the motor, between 0 and [Rated motor volt.] (UnS)
[Mot thermal] (tHr): Motor thermal state, between 0 and 200% of the rated thermal state
[Mot therm2] (tHr2): Motor thermal state 2, between 0 and 200 % of the rated thermal state
[Mot therm3] (tHr3): Motor
thermal state 3, between 0 and 200% of the rated thermal state
[Drv thermal] (tHd): Drive thermal state, between 0 and 200% of the rated thermal state
[Torque lim.] (tqL): Torque limit, between 0 and 3 times the rated motor torque
[dO1] (dO1): Assignment to a logic output. This assignment can only appear if [DO1 assignment] (dO1) has been assigned.
This is the only possible choice in this case, and is only displayed for informational purposes.
[Torque 4Q] (tqMS): Signed motor torque, between -3 and +3 times the rated motor torque. The + sign and the - sign
correspond to the physical direction of the torque, regardless of mode (motor or generator).
[OA01] (OA01): Function blocks: Analog Output 01
...
[OA10] (OA10): Function blocks: Analog Output 10
AO1t [AO1 Type]
[Current] (0A)
10U
0A
[Voltage] (10U): Voltage output
[Current] (0A): Current output
AOL1 [AO1 min Output]
0 to 20.0 mA 0 mA
g
This parameter can be accessed if [AO1 Type] (AO1t ) is set to [Current] (0A).
AOH1 [AO1 max Output]
0 to 20.0 mA 20.0 mA
g
This parameter can be accessed if [AO1 Type] (AO1t ) is set to [Current] (0A).
UOL1 [AO1 min Output]
0 to 10.0 V 0 V
g
This parameter can be accessed if [AO1 Type] (AO1t ) is set to [Voltage] (10U).
UOH1 [AO1 max Output]
0 to 10.0 V 10.0 V
g
This parameter can be accessed if [AO1 Type] (AO1t ) is set to [Voltage] (10U).
ASL1 [Scaling AO1 min]
0 to 100.0% 0%
Scaling of the lower limit of the assigned parameter, as a % of the maximum possible variation.
ASH1 [Scaling AO1 max]
0 to 100.0% 100.0%
Scaling of the upper limit of the assigned parameter, as a % of the maximum possible variation.
AO1F [AO1 Filter]
0 to 10.00 s 0 s
Interference filtering. This parameter is forced to 0 if [AO1 assignment] (AO1) is set to [dO1] (dO1).
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
DRI- > CONF > FULL > I_O- > AO1-