Installation manual

Configuration Mode (ConF)
130 S1A28692 03/2010
Parameters described in this page can be accessed by:
The following submenus group the alarms into 1 to 3 groups, each of which can be assigned to a relay or a
logic output for remote signaling. These groups can also be displayed on the graphic display terminal (see
[3.3 MONITORING CONFIG.] (MCF-) menu page 266
) and viewed via the [1.2 MONITORING] (MOn-)
menu page 41
.
When one or a number of alarms selected in a group occurs, this alarm group is activated.
Code Name / Description
I_O- [INPUTS / OUTPUTS CFG] (continued)
A1C- [ALARM GRP1 DEFINITION]
PLA
EFA
USA
CtA
FtA
F2A
SrA
tSA
tS2
tS3
UPA
FLA
tHA
PEE
PFA
AP3
SSA
tAd
tJA
ULA
OLA
rSdA
ttHA
ttLA
FqLA
dLdA
Selection to be made from the following list:
[LI6=PTC al.] (PLA): LI6 = PTCL alarm
[Ext. fault al.] (EFA): External fault alarm
[Under V. al.] (USA): Undervoltage alarm
[I attained] (CtA): Current threshold attained ([Current threshold] (Ctd) page 89
)
[Freq.Th.att.] (FtA): Frequency threshold attained ([Freq. threshold] (Ftd) page 89
)
[Freq. Th. 2 attain.] (F2A): Frequency threshold 2 attained ([Freq. Th. 2 attain] (F2d) page 89
)
[Freq.ref.att] (SrA): Frequency reference attained
[Th.mot. att.] (tSA): Motor 1 thermal state attained
[Th.mot2 att] (tS2): Motor 2 thermal state attained
[Th.mot3 att] (tS3): Motor 3 thermal state attained
[Uvolt warn] (UPA): Undervoltage threshold
[HSP attain.] (FLA): High speed attained
[Al. °C drv] (tHA): Drive overheating
[[PID error al] (PEE): PID error alarm
[PID fdbk al.] (PFA): PID feedback alarm
[AI3 Al. 4-20] (AP3): Alarm indicating absence of 4-20 mA signal on input AI3
[Lim T/I att.] (SSA): Torque limit alarm
[Th. drv. att.] (tAd): Drive thermal state attained
[IGBT alarm] (tJA): IGBT alarm
[Underload. Proc. Al.] (ULA): Underload alarm
[Overload. Proc. Al.] (OLA): Overload alarm
[Rope slack alarm] (rSdA): Rope slack (see [Rope slack config.] (rSd) parameter page 190
)
[High torque alarm] (ttHA): Motor torque overshooting high threshold [High torque thd.] (ttH) page 89
.
[Low torque alarm] (ttLA): Motor torque undershooting low threshold[Low torque thd.] (ttL) page 89
.
[Freq. meter Alarm] (FqLA): Measured speed threshold attained: [Pulse warning thd.] (FqL) page 89
.
[Dynamic load alarm] (dLdA): Load variation detection (see [DYNAMIC LOAD DETECT.] (dLd-) page 248
).
See the multiple selection procedure on page 33
for the integrated display terminal, and page 24 for the graphic display terminal.
A2C- [ALARM GRP2 DEFINITION]
Identical to [ALARM GRP1 DEFINITION] (A1C-) page 130.
A3C- [ALARM GRP3 DEFINITION]
Identical to [ALARM GRP1 DEFINITION] (A1C-) page 130.
DRI- > CONF > FULL > I_O- > A1C-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com