Installation manual

Configuration Mode (ConF)
136 S1A28692 03/2010
Command channel for [I/O profile] (IO) configuration
Separate reference and command, as in [Separate] (SEP) configuration
The command channels Cd1 and Cd2 are independent of the reference channels Fr1, Fr1b and
Fr2.
Cd1, Cd2:
Terminals, graphic display terminal, integrated Modbus, integrated CANopen®, communication card
A command or an action can be assigned:
To a fixed channel by selecting an LI input or a Cxxx bit:
- By selecting, for example, LI3, this action will be triggered by LI3 regardless of which command
channel is switched.
- By selecting, for example, C214, this action will be triggered by integrated CANopen® with bit 14
regardless of which command channel is switched.
To a switchable channel by selecting a CDxx bit:
- By selecting, for example, Cd11, this action will be triggered by:
LI12 if the terminals channel is active
C111 if the integrated Modbus channel is active
C211 if the integrated CANopen® channel is active
C311 if the communication card channel is active
If the active channel is the graphic display terminal, the functions and commands assigned to CDxx switchable
internal bits are inactive.
Note: Cd06 to Cd13 can only be used for switching between 2 networks. They do not have equivalent
logic inputs.
/4/2
//;
/@%
279
:;I
/@$
(Stop Key priority)
Forced local
Parameter:
The black square represents the factory
setting assignment, except for [Profile].
Forward
Reverse
STOP
Key:
Graphic display
terminal
nO
[Cmd channel 1]
[Cmd channel 2]
[Cmd switching]
[Profile]
YES
SEP
STOP
CMD
LI