Installation manual

Configuration Mode (ConF)
138 S1A28692 03/2010
Assignment conditions for logic inputs and control bits
The following elements are available for every command or function that can be assigned to a logic input or a
control bit:
Note: In [I/O profile] (IO) configuration, LI1 cannot be accessed and if [2/3 wire control] (tCC) page
73
is set to [3 wire] (3C), LI2, C101, C201 and C301 cannot be accessed either.
[LI1] (LI1) to [LI6] (LI6) Drive with or without option
[LAI1] (LAI1) to [LAI2] (LAI2) Logical inputs
[C101] (C101) to [C110] (C110) With integrated Modbus in [I/O profile] (IO) configuration
[C111] (C111) to [C115] (C115) With integrated Modbus regardless of configuration
[C201] (C201) to [C210] (C210) With integrated CANopenĀ® in [I/O profile] (IO) configuration
[C211] (C211) to [C215] (C215) With integrated CANopenĀ® regardless of configuration
[C301] (C301) to [C310] (C310) With a communication card in [I/O profile] (IO) configuration
[C311] (C311) to [
C315] (C315) With a communication card regardless of configuration
[CD00] (Cd00) to [CD10] (Cd10) In [I/O profile] (IO) configuration
[CD11] (Cd11) to [CD15] (Cd15) Regardless of configuration
[OL01] (OL01) to [OL10] (OL10) Regardless of configuration
WARNING
LOSS OF CONTROL
Inactive communication channels are not monitored (no trip in the event of a communication bus
interruption).
Check that the commands and functions assigned to bits C101 to C315 will not pose a risk in the event of
the interruption of the associated communication bus.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com