Installation manual
Setup
14 S1A28692 03/2010
Steps for setting-up the drive
2. Apply input power to the drive, but do not give a run
command.
3. Configure:
• The nominal frequency of the motor
[Standard mot. freq] (bFr) page 74
if this is not 50 Hz.
• The motor parameters in the [MOTOR CONTROL] (drC-)
menu, page 92
, only if the factory configuration of the drive is not
suitable.
• The application functions in the
[INPUTS / OUTPUTS CFG] (I_O-) menu, page 112
, the
[COMMAND] (CtL-) menu, page 139, and the
[APPLICATION FUNCT.] (FUn-) menu, page 152
, only if the
factory configuration of the drive is not suitable.
5. Start the drive.
1. Please refer to the installation manual.
PROGRAMMING
INSTALLATION
4. In the [SETTINGS] (SEt-) menu, adjust
the following parameters:
•
[Acceleration] (ACC), page 75 and
[Deceleration] (dEC), page 75.
• [Low speed] (LSP), page 75 and
[High speed] (HSP), page 77.
• [Mot. therm. current] (ItH), page 75.
Tips:
• Before beginning programming, complete the customer
setting tables, page 301
.
• Use the [Restore config.] (FCS) parameter, page 69, to
return to the factory settings at any time.
• To locate the description of a function quickly, use the index
of functions page 299
.
• Before configuring a function, read carefully the "Function
compatibility" section page 150
.
Note: The following operations must be performed for
optimum drive performance in terms of accuracy and
response time:
• Enter the values indicated on the motor rating plate in the
[MOTOR CONTROL] (drC-) menu, page 92
.
• Perform auto-tuning with the motor cold and connected
using the [Auto-tuning] (tUn) parameter, page 75
.