Installation manual

Configuration Mode (ConF)
144 S1A28692 03/2010
Parameters described in this page can be accessed by:
FbrM [FB start mode]
[No] (nO)
DANGER
UNINTENDED EQUIPMENT OPERATION
Start mode value will allow the start of the program by the selected channel.
Check that this configuration will not endanger personnel or equipment in any way.
Failure to follow these instructions will result in death or serious injury.
nO
YES
LI1
...
Allows to choose the different ways of starting the Function blocks application.
Note: Modifications of this parameter are not taken into account if the Function blocks application is running.
[No] (nO): Function blocks application is controlled by [FB command] (FbCd) parameter
[Yes] (YES): Function blocks application switches to Run automatically at drive power on
[LI1] (LI1): Function blocks application switches to Run on a rising edge of the logic input. It switch to Stop on falling edge of
the logic input.
[...] (...): See the assignment conditions on page 138
(not [OL10] (OL01) to [OL10] (OL10)).
FbSM [FB Stop mode]
[Freewheel] (YES)
WARNING
LOSS OF CONTROL
If [FB stop mode] (FbSM) is set to [No] (nO) the motor will not stop when the program will be stopped.
Do not select these values unless exterior stopping methods exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
nO
YES
rMP
FSt
dCI
Allows to setup the way of working of the drive when function blocks are stopped.
[Ignore] (nO): The drive ignores the detected fault
[Freewheel] (YES): Motor stops in freewheel
[Ramp stop] (rMP): Ramp stop
[Fast stop] (FSt): Fast stop
[DC injection] (dCI): DC injection
FbdF [FB on drive fault]
[Stop] (StOP)
StOP
IGn
Behavior of function blocks when the drive trips.
[Stop] (StOP): Function blocks stops when the drive trips, outputs are realeased
[Ignore] (IGn): Function blocks continue to work when the drive trips (except CFF and INFE)
FbA- [INPUTS ASSIGNMENTS]
IL01 [Logic input 1 assignment]
[No] (nO)
nO
FLt
FtA
F2A
Fr1
Fr2
Cd1
Cd2
Fr1b
YES
LI1
...
Possible assignment for the Function block logic input.
[No] (nO): Not assigned
[No drive flt] (FLt): Drive fault detection status (relay normally energized, and de-energized if there is a trip)
[Freq. Th. attain.] (FtA): Frequency threshold attained ([Freq. threshold] (Ftd) page 89
)
[Freq. Th 2 attain.] (F2A): Frequency threshold 2 attained ([Freq. threshold 2] (F2d) page 89
)
[Ref.1 channel] (Fr1) Reference source 1
[Ref.2 channel] (Fr2) Reference source 2
[ch1 active] (Cd1): Command channel = channel 1 (for CSS)
[ch2 active] (Cd2): Command channel = channel 2 (for CSS)
[Ref.1B channel] (Frlb): Reference channel = channel 1b (for RFC)
[Yes] (YES): Yes
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
IL-- [Logic input x assignment]
[No] (nO)
All the Function Blocks logic inputs available on the drive are processed as in the example for
[Logic input 1 assignment] (IL01) above, up to [Logic input 10 assignment] (IL10).
Code Name / Description Adjustment range Factory setting
2 s
DRI- > CONF > FULL > FBM-