Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 153
Parameters described in this page can be accessed by:
REFERENCE OPERATIONS
Summing input / Subtracting input / Multiplier
A = (Fr1 or Fr1b + SA2 + SA3 - dA2 - dA3) x MA2 x MA3
If SA2, SA3, dA2, dA3 are not assigned, they are set to 0.
If MA2, MA3 are not assigned, they are set to 1.
A is limited by the minimum LSP and maximum HSP parameters.
For multiplication, the signal on MA2 or MA3 is interpreted as a %. 100% corresponds to the maximum
value of the corresponding input. If MA2 or MA3 is sent via the communication bus or graphic display
terminal, an MFr multiplication variable, page 266 must be sent via the bus or graphic display terminal.
Reversal of the direction of operation in the event of a negative result can be inhibited (see
[RV Inhibition] (SIn) page 139).
Fr1 or Fr1b
SA2
SA3
dA2
dA3
MA2
MA3
A
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
OAI- [REF. OPERATIONS]
Reference = (Fr1 or Fr1b + SA2 + SA3 - dA2 - dA3) x MA2 x MA3. See the diagrams on pages 132 and 133.
Note: This function cannot be used with certain other functions. Follow the instructions on page 148
.
SA2 [Summing ref. 2]
[No] (nO)
nO
A11
A12
A13
LCC
Mdb
CAn
nEt
PI
AIU1
AIU2
OA01
...
OA10
Selection of a reference to be added to [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).
[No] (nO): Not assigned
[Al1] (A11): Analog input A1
[Al2] (A12): Analog input A2
[Al3] (A13): Analog input A3
[HMI] (LCC): Graphic display terminal or remote display terminal source
[Modbus] (Mdb): Integrated Modbus
[CANopen] (CAn): Integrated CANopen®
[Com. card] (nEt): Communication option board source
[RP] (PI): Motor voltage
[AI virtual 1] (AIU1): Virtual analog input 1 with the jog dial
[AI virtual 2] (AIU2)
: Vir
tual analog input 2 by the communication bus
[OA01] (OA01): Function blocks: Analog Output 01
...
[OA10] (OA10): Function blocks: Analog Output 10
SA3 [Summing ref. 3]
[No] (nO)
Selection of a reference to be added to [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).
Identical to [Summing ref. 2] (SA2) page 153
.
dA2 [Subtract. ref. 2]
[No] (nO)
Selection of a reference to be subtracted from [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).
Identical to [Summing ref. 2] (SA2) page 153
.
DRI- > CONF > FULL > FUN- > OAI-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com