Configuration Mode (ConF)
162 S1A28692 03/2010
Parameters described in this page can be accessed by:
(1) The parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) In corresponds to the rated drive current indicated in the Installation manual and on the drive nameplate.
SdC2 [Auto DC inj. level 2]
0 to 1.2 In (2) 0.5 In (2)
g
T
(1)
CAUTION
RISK OF DAMAGE TO THE MOTOR
Check that the motor will withstand this current without overheating.
Failure to follow these instructions can result in equipment damage.
2nd level of standstill DC injection current.
This parameter can be accessed if [Auto DC injection] (AdC) is not [No] (nO).
tdC2 [Auto DC inj. time 2]
0 to 30 s 0 s
g
T
(1)
CAUTION
RISK OF DAMAGE TO THE MOTOR
• Long periods of DC injection braking can cause overheating and damage the motor.
• Protect the motor by avoiding long periods of DC injection braking.
Failure to follow these instructions can result in equipment damage.
2nd standstill injection time.
This parameter can be accessed if [Auto DC injection] (AdC) is set to [Yes] (YES).
Code Name / Description Adjustment range Factory setting
AdC SdC2 Operation
YES x
Ct
0
Ct
= 0
Run command
Speed
t
SdC1
SdC2
tdC1 tdC1 + tdC2
I
t
SdC1
I
t
SdC1
SdC2
tdC1
I
t
0
t
1
0
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
To change the assignment of this parameter, press the ENT key for 2 s.
2 s
DRI- > CONF > FULL > FUN- > ADC-