Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 165
PRESET SPEEDS
2, 4, 8 or 16 speeds can be preset, requiring 1, 2, 3 or 4 logic inputs respectively.
Note:
You must configure 2 and 4 speeds in order to obtain 4 speeds.
You must configure 2, 4 and 8 speeds in order to obtain 8 speeds.
You must configure 2, 4, 8, and 16 speeds in order to obtain 16 speeds.
Combination table for preset speed inputs
(1) See the diagram on page 132: Reference 1 = (SP1).
16 speeds
LI (PS16)
8 speeds
LI (PS8)
4 speeds
LI (PS4)
2 speeds
LI (PS2)
Speed reference
0 000Reference (1)
0 001SP2
0 010SP3
0 011SP4
0 100SP5
0 101SP6
0 110SP7
0 111SP8
1 000SP9
1 001SP10
1 010SP11
1 011SP12
1 100SP13
1 101SP14
1 110SP15
1 111SP16