Installation manual

Configuration Mode (ConF)
170 S1A28692 03/2010
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
UPd- [+/- SPEED]
This function can be accessed if reference channel [Ref.2 channel] (Fr2) is set to [+/-Speed] (UPdt), see page 140.
Note: This function cannot be used with certain other functions. Follow the instructions on page 148
.
USP [+ speed assignment]
[No] (nO)
nO
LI1
...
Function active if the assigned input or bit is at 1.
[No] (nO): Not assigned
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
dSP [-Speed assignment]
[No] (nO)
See the assignment conditions on page 138
Function active if the assigned input or bit is at 1.
Str [Reference saved]
[No] (nO)
g
Associated with the "+/- speed" function, this parameter can be used to save the reference:
- When the run commands disappear (saved to RAM).
- When the line supply or the run commands disappear (saved to EEPROM).
Therefore, the next time the drive starts up, the speed reference is the last reference saved.
nO
rAM
EEP
[No] (nO): No save (the next time the drive starts up, the speed reference is [Low speed] (LSP), see page 75)
[RAM] (rAM): Saved in RAM
[EEprom] (EEP): Saved in EEPROM
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
DRI- > CONF > FULL > FUN- > UPD-