Configuration Mode (ConF)
S1A28692 03/2010 173
Parameters described in this page can be accessed by:
REFERENCE MEMORIZING
Saving a speed reference value using a logic input command lasting longer than 0.1 s.
This function is used to control the speed of several drives alternately via a single analog reference and one
logic input for each drive.
It is also used to confirm a line reference (communication bus or network) on several drives via a logic input.
This allows movements to be synchronized by getting rid of variations when the reference is set.
The reference is acquired 100 ms after the rising edge of the request. A new reference is not then acquired
until a new request is made.
t
t
t
0
0
1
0
1
100 ms
100 ms100 ms
F: Motor frequency
Reference
Run command
LIx (saved)
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
SPM- [MEMO REFERENCE]
SPM [Ref. memo ass.]
[No] (nO)
nO
LI1
...
Assignment to a logic input.
Function active if the assigned input is at active state.
[No] (nO): Not assigned
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
DRI- > CONF > FULL > FUN- > SPM-