Configuration Mode (ConF)
S1A28692 03/2010 173
Parameters described in this page can be accessed by:
REFERENCE MEMORIZING
Saving a speed reference value using a logic input command lasting longer than 0.1 s.
• This function is used to control the speed of several drives alternately via a single analog reference and one
logic input for each drive.
• It is also used to confirm a line reference (communication bus or network) on several drives via a logic input.
This allows movements to be synchronized by getting rid of variations when the reference is set.
• The reference is acquired 100 ms after the rising edge of the request. A new reference is not then acquired
until a new request is made.
t
t
t
0
0
1
0
1
100 ms
100 ms100 ms
F: Motor frequency
Reference
Run command
LIx (saved)
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
SPM- [MEMO REFERENCE]
SPM [Ref. memo ass.]
[No] (nO)
nO
LI1
...
Assignment to a logic input.
Function active if the assigned input is at active state.
[No] (nO): Not assigned
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
DRI- > CONF > FULL > FUN- > SPM-