Installation manual

Overview
18 S1A28692 03/2010
Factory configuration
Factory settings
The Altivar 32 is factory-set for common operating conditions:
Display: drive ready [Ready] (rdY) when motor is ready to run and motor frequency when motor is
running.
The LI3 to LI6 logic inputs, AI2 and AI3 analog inputs, LO1 logic output, AO1 analog output, and R2 relay
are unassigned.
Stop mode when fault detected: freewheel.
Note: If you want to keep the drive presettings to a minimum, select the macro configuration
[Macro configuration] (CFG) = [Start/stop] (StS) followed by
[Restore config.] (FCS) = [Config. CFG] (InI). For more information, see page 70
.
Check whether the values above are compatible with the application.
Code Description Factory settings values Page
bFr [Standard mot. freq] [50Hz IEC] 74
tCC [2/3 wire control] [2 wire] (2C): 2-wire control 73
Ctt [Motor control type] [Standard] (Std): U/F 2 points (Volts/Hz) without internal speed loop 92
ACC [Acceleration] 3.0 seconds 75
dEC [Deceleration] 3.0 seconds 75
LSP [Low speed] 0 Hz 75
HSP [High speed] 50 Hz 75
ItH [Mot. therm. current] Nominal motor current (value depending on drive rating) 75
SdC1 [Auto DC inj. level 1] 0.7 x nominal drive current, for 0.5 seconds 81
SFr [Switching freq.] 4 kHz 82
Frd [Forward] [LI1] (LI1): Logic input LI1 113
rrS [Reverse assign.] [LI2] (LI2): Logic input LI2 113
Fr1 [Ref.1 channel] [AI1] (AI1): Analog input AI1 139
r1 [R1 Assignment] [No drive flt] (FLt): The contact opens when a fault is detected or
when the drive has been switched off
123
brA [Dec ramp adapt.] [Yes] (YES): Function active (automatic adaptation of deceleration
ramp)
157
Atr [Automatic restart] [No] (nO): Function inactive 234
Stt [Type of stop] [Ramp stop] (rMP): On ramp 158
CFG [Macro configuration] [Start/Stop] (StS) 70