Installation manual

Configuration Mode (ConF)
200 S1A28692 03/2010
Parameters described in this page can be accessed by:
PID PRESET REFERENCES
(1) The parameter can also be accessed in the [SETTINGS] (SEt-) menu.
(2) If a graphic display terminal is not in use, values greater than 9,999 will be displayed on the 4-digit display with a period
mark after the thousand digit, for example, 15.65 for 15,650.
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
PrI- [PID PRESET REFERENCES]
Function can be accessed if [PID feedback ass.] (PIF) page 196 is assigned.
Pr2 [2 preset PID ref.]
[No] (nO)
nO
LI1
...
If the assigned input or bit is at 0, the function is inactive.
If the assigned input or bit is at 1, the function is active.
[No] (nO): Not assigned
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
Pr4 [4 preset PID ref.]
[No] (nO)
Check that [2 preset PID ref.] (Pr2) has been assigned before assigning this function.
Identical to [2 preset PID ref.] (Pr2) page 198
.
If the assigned input or bit is at 0, the function is inactive.
If the assigned input or bit is at 1, the function is active.
rP2 [2 preset PID ref.]
[Min PID reference] (PIP1) to
[Max PID reference] (PIP2) (2)
300
g
T
(1)
This parameter can be accessed if [Preset ref. PID 2] (Pr2) is assigned.
rP3 [3 preset PID ref.]
[Min PID reference] (PIP1) to
[Max PID reference] (PIP2) (2)
600
g
T
(1)
This parameter can be accessed if [Preset ref. PID 3] (Pr3) is assigned.
rP4 [4 preset PID ref.]
[Min PID reference] (PIP1) to
[Max PID reference] (PIP2) (2)
900
g
T
(1)
This parameter can be accessed if [Preset ref. PID 4] (Pr4) is assigned.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
DRI- > CONF > FULL > FUN- > PRI-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com