Configuration Mode (ConF)
202 S1A28692 03/2010
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
tOL- [TORQUE LIMITATION]
tLA [Torque limit. activ.]
[No] (nO)
nO
YES
LI1
...
If the assigned input or bit is at 0, the function is inactive.
If the assigned input or bit is at 1, the function is active.
[No] (nO): Function inactive
[Yes] (YES): Function always active
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
IntP [Torque increment]
[1%] (1)
g
This parameter cannot be accessed if [Torque limit. activ.] (tLA) is set to [No] (nO).
Selection of units for the [Motoring torque lim] (tLIM ) and [Gen. torque lim] (tLIG) parameters.
0.1
1
[0,1%] (0.1): Unit 0.1%
[1%] (1): Unit 1%
tLIM [Motoring torque lim]
0 to 300% 100%
g
T
(1)
This parameter cannot be accessed if [Torque limit. activ.] (tLA) is set to [No] (nO).
Torque limitation in motor mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque increment] (IntP) parameter.
tLIG [Gen. torque lim]
0 to 300% 100%
g
T
(1)
This parameter cannot be accessed if [Torque limit. activ.] (tLA) is set to [No] (nO).
Torque limitation in generator mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque increment] (IntP) parameter.
tAA [Torque ref. assign.]
[No] (nO)
nO
AI1
AI2
AI3
PI
AIU1
AIU2
OA01
...
OA10
If the function is assigned, the limitation varies between 0% and 300% of the rated torque on the basis of the 0% to 100% signal
applied to the assigned input.
Examples:
12 mA on a 4-20 mA input results in limitation to 150% of the rated torque.
2.5 V on a 10 V input results in 75% of the rated torque.
[No] (nO): Not assigned (function inactive)
[AI1] (AI1): Analog input
[AI2] (AI2): Analog input
[AI3] (AI3): Analog input
[RP] (PI): Pulse input
[AI Virtual 1] (AIU1): Virtual analog input 1 with the jog dial
[AI Virtual 2] (AIU2): Virtual input via communication bus, to be configured via [AI2 net. channel] (AIC2) page 122
.
[OA01] (OA01): Function blocks: Analog Output 01
...
[OA10] (OA10): Function blocks: Analog Output 10