Installation manual

Configuration Mode (ConF)
206 S1A28692 03/2010
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
LLC- [LINE CONTACTOR COMMAND]
LLC [Line contactor ass.]
[No] (nO)
nO
LO1
r2
dO1
Logic output or control relay.
[No] (nO): Function not assigned (in this case, none of the function parameters can be accessed)
[LO1] (LO1): Logical output LO1
[R2] (r2): Relay r2
[d01] (dO1): Analog output AO1 functioning as a logic output. Selection can be made if [AO1 assignment] (AO1) page 129
is set to [No] (nO)
LES [Drive lock]
[No] (nO)
g
This parameter can be accessed if [Line contactor ass.] (LLC) is not set to [No] (nO).
The drive locks when the assigned input or bit changes to 0.
nO
LI1
...
[No] (nO): Function inactive
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
LCt [Mains V. time out]
5 to 999 s 5 s
g
Monitoring time for closing of line contactor. If, once this time has elapsed, there is no voltage on the drive power circuit, the
drive will lock with a [Line contactor] (
LCF) detected fault.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
DRI- > CONF > FULL > FUN- > LCC-