Configuration Mode (ConF)
208 S1A28692 03/2010
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
OCC- [OUTPUT CONTACTOR CMD]
OCC [Out. contactor ass.]
[No] (nO)
nO
LO1
r2
dO1
Logic output or control relay.
[No] (nO): Function not assigned (in this case, none of the function parameters can be accessed)
[LO1] (LO1): Logical output LO1
[R2] (r2): Relay r2
[dO1] (dO1): Analog output AO1 functioning as a logic output. Selection can be made if [AO1 assignment] (AO1) page 129
is set to [No] (nO)
rCA [Output contact. fdbk]
[No] (nO)
nO
LI1
...
The motor starts up when the assigned input or bit changes to 0.
[No] (nO): Function inactive
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
dbS [Delay to motor run]
0.05 to 60 s 0.15 s
g
T
Time delay for:
Motor control following the sending of a run command
Output contactor state monitoring, if the feedback is assigned. If the contactor fails to close at the end of the set time, the drive
will lock in FCF2 mode.
This parameter can be accessed if [Out. contactor ass.] (OCC) is assigned or if [Output contact. fdbk] (rCA) is assigned.
The time delay must be greater than the closing time of the output contactor.
dAS [Delay to open cont.]
0 to 5.00 s 0.10 s
g
T
Time delay for output contactor opening command following motor stop.
This parameter can be accessed if [Output contact. fdbk] (rCA) is assigned.
The time delay must be greater than the opening time of the output contactor. If it is set to 0, the detected fault will not be
monitored.
If the contactor fails to open at the end of the set time, the drive will lock in FCF1 fault mode.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
DRI- > CONF > FULL > FUN- > OCC-