Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 215
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
MLP- [PARAM. SET SWITCHING]
CHA1 [2 parameter sets]
[No] (nO)
nO
FtA
F2A
LI1
...
Switching 2 parameter sets.
[No] (nO): Not assigned
[Freq. Th.att.] (FtA): Switching via [Freq. threshold] (Ftd) page 234
[Freq. Th. 2 att.] (F2A): Switching via [Freq. threshold 2] (F2d) page 234
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
CHA2 [3 parameter sets]
[No] (nO)
Identical to [2 parameter sets] (CHA1) page 215
.
Switching 3 parameter sets.
Note: In order to obtain 3 parameter sets, [2 parameter sets] (CHA1) must also be configured.
SPS [PARAMETER SELECTION]
This parameter can only be accessed on the graphic display terminal if [2 parameter sets] (CHA1) is not set to [No] (nO).
Making an entry in this parameter opens a window containing all the adjustment parameters that can be accessed.
Select 1 to 15 parameters using ENT (a then appears next to the parameter). Parameter(s) can also be deselected using
ENT.
Example:
MLP- [PARAM. SET SWITCHING] (continued)
PS1- [SET 1]
g
T
S101
...
S115
This parameter can be accessed if at least 1 parameter has been selected in [PARAMETER SELECTION].
Making an entry in this parameter opens a settings window containing the selected parameters in the order in which they were
selected.
With the graphic display terminal:
With the integrated display terminal:
Proceed as in the Settings menu using the parameters that appear.
MLP- [PARAM. SET SWITCHING] (continued)
PS2- [SET 2]
g
T
S201
...
S215
This parameter can be accessed if at least 1 parameter has been selected in [PARAMETER SELECTION].
Identical to [SET 1] (PS1-) page 215
.
PARAMETER SELECTION
SETTINGS
Ramp increment
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
RDY Term +0.0 Hz 0.0 A
SET1
Acceleration : 9.51 s
Deceleration : 9.67 s
Acceleration 2 : 12.58 s
Deceleration 2 : 13.45 s
Begin Acc round: 2.3 s
Code Quick
ENT
RDY Term +0.0 Hz 0.0 A
Acceleration
9.51 s
Min = 0.1 Max = 999.9
<< >> Quick
DRI- > CONF > FULL > FUN- > MLP-