Installation manual

Configuration Mode (ConF)
218 S1A28692 03/2010
Transfer of a drive configuration to another one, with graphic display terminal, when the drive uses
[MULTIMOTORS/CONFIG.] (MMC-) function
Let A be the source drive and B the drive addressed. In this example, switching is controlled by logic input.
1. Connect graphic display terminal to the drive A.
2. Put logic input LI ([2 Configurations] (CnF1)) and LI ([3 Configurations]
(CnF2)) to 0.
3. Download configuration 0 in a file of graphic display terminal (example: file 1 of the graphic display terminal).
4. Put logic input LI ([2 Configurations]
(CnF1)) to 1 and leave logic input LI ([3 Configurations] (CnF2))
to 0.
5. Download configuration 1 in a file of graphic display terminal (example: file 2 of the graphic display terminal).
6. Put logic input LI ([3 Configurations]
(CnF2)) to 1 and leave logic input LI ([2 Configurations] (CnF1))
to 1.
7. Download configuration 2 in a file of graphic display terminal (example: file 3 of the graphic display terminal).
8. Connect graphic display terminal to the drive B.
9. Put logic input LI ([2 Configurations] (CnF1)) and LI ([3 Configurations] (CnF2)) to 0.
10. Make a factory setting of the drive B.
11. Download the configuration file 0 in the drive (file 1 of graphic display terminal in this example).
12. Put logic input LI ([2 Configurations] (CnF1)) to 1 and leave logic input LI
([3 Configurations] (CnF2)) to 0.
13. Download the configuration file 1 in the drive (file 2 of graphic display terminal in this example).
14. Put logic input LI ([3 Configurations]
(CnF2)) to 1 and leave logic input LI
([2 Configurations] (CnF1)) to 1.
15. Download the configuration file 2 in the drive (file 3 of graphic display terminal in this example).
Note: Steps 6, 7, 14 et 15 are necessary only if [MULTIMOTORS/CONFIG.] (MMC-) function is used with
3 configurations or 3 motors.
Switching command
Depending on the number of motors or selected configurations (2 or 3), the switching command is sent using
one or two logic inputs. The table below lists the possible combinations.
Configuration 0
or motor 0
Configuration 1
or motor 1
Configuration 2
or motor 2
Current
configuration
Graphic display
terminal
Network
Terminal
CANopenĀ®
Modbus
[2 Configurations] (CnF1)
[3 Configurations] (CnF2)
CnF1 = 0, CnF2 = 0
CnF1 = 1, CnF2 = 0 CnF1 = 0, CnF2 = 1
or
CnF1 = 1, CnF2 = 1