Installation manual

Configuration Mode (ConF)
220 S1A28692 03/2010
Parameters described in this page can be accessed by:
Configuration information output
In the [INPUTS / OUTPUTS CFG] (I_O-) menu, a logic output can be assigned to each configuration or
motor (2 or 3) for remote information transmission.
Note: As the [INPUTS / OUTPUTS CFG] (I_O-) menu is switched, these outputs must be assigned in all
configurations in which information is required.
CAUTION
RISK OF DAMAGE TO THE MOTOR
The motor thermal state of each motor is not memorized when power is switched off.
To continue to protect the motors, it is required to:
• Perform auto-tuning on each motor every time the power is switched on,
or
• Use an external overload protection on each motor.
Failure to follow these instructions can result in equipment damage.
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
MMC- [MULTIMOTORS/CONFIG.]
CHM [Multimotors]
[No] (nO)
CAUTION
RISK OF DAMAGE TO THE MOTOR
When [Multimotors] (CHM) is set to [Yes] (YES), the motor thermal state of each motor is not memorized
when power is switched off.
To continue to protect the motors, it is required to :
• Perform auto-tuning on each motor every time the power is switched on,
or
• Use an external overload protection on each motor.
Failure to follow these instructions can result in equipment damage.
nO
YES
[No] (nO): Multiconfiguration possible
[Yes] (YES): Multimotor possible
CnF1 [2 Configurations]
[No] (nO)
nO
LI1
...
Switching of 2 motors or 2 configurations.
[No] (nO): No switching
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
CnF2 [3 Configurations]
[No] (nO)
Switching of 3 motors or 3 configurations.
Identical to [2 Configurations] (CnF1) page 220
.
Note: In order to obtain 3 motors or 3 configurations, [2 Configurations] (CnF1) must also be configured.
DRI- > CONF > FULL > FUN- > MMC-