Configuration Mode (ConF)
S1A28692 03/2010 229
Parameters described in this page can be accessed by:
HIGH SPEED SWITCHING
Code Name / Description Adjustment range Factory setting
FUn- [APPLICATION FUNCT.] (continued)
CHS- [HSP SWITCHING]
SH2 [2 High speed]
[No] (nO)
nO
FtA
F2A
LI1
...
High Speed Switching.
[No] (nO): Function not assigned
[Freq. Th. attain.] (FtA): Frequency threshold attained
[Freq. Th 2 attain.] (F2A): Frequency threshold 2 attained
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
SH4 [4 High speed]
[No] (nO)
High Speed Switching.
Note: In order to obtain 4 High speed, [2 High speed] (SH2) must also be configured.
Identical to [2 High speed] (SH2) page 229
.
HSP
T
[High speed]
0 to 599 Hz 50 Hz
Motor frequency at maximum reference, can be set between [Low speed] (LSP) and [Max frequency] (tFr).
The factory setting changes to 60 Hz if [Standard mot. freq] (bFr) is set to [60Hz NEMA] (60).
HSP2 [High speed 2]
0 to 599 Hz 50 Hz
g
T
Visible if [2 High speed] (SH2) is not set to [No] (nO).
Identical to [High speed] (HSP) page 229
.
HSP3 [High speed 3]
0 to 599 Hz 50 Hz
g
T
Visible if [4 High speed] (SH4) is not set to [No] (nO).
Identical to [High speed] (HSP) page 229
.
HSP4 [High speed 4]
0 to 599 Hz 50 Hz
g
T
Visible if [4 High speed] (SH4) is not set to [No] (nO).
Identical to [High speed] (HSP) page 229
.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
DRI- > CONF > FULL > FUN- > CHS-