Parameters described in this page can be accessed by:
PTC probe
1 set of PTC probe can be managed by the drive in order to help to protect the motor: on logic input LI6
converted for this use by switch SW2 on the control block.
The PTC probe is monitored for the following detected faults:
Motor overheating
Sensor break
Sensor short-circuit
Protection via PTC probe does not disable protection via I
2
t calculation performed by the drive (the two types
of protection can be combined).
R1A
R1B
R1C
COM
AO1
COM
AI3
AI2
10V
AI1
COM
+24
P24
STO
LO+
LO-
LI6
LI5
LI4
LI3
LI2
LI1
R2C
R2A
SW1
SW2
LI6
PTC
Source
Sink ext.
Sink int.
Code Name / Description Adjustment range Factory setting
FULL [FULL] (continued)
FLt- [FAULT MANAGEMENT]
PtC- [PTC MANAGEMENT]
PtCL [LI6 = PTC probe]
[No] (nO)
nO
AS
rdS
rS
Check first that the switch SW2 on the control block is set to PTC.
[No] (nO): Not used
[Always] (AS): PTC probe are monitored permanently, even if the power supply is not connected (as long as the control remains
connected to the power supply)
[Power ON] (rdS): PTC probe are monitored while the drive power supply is connected
[Motor ON] (rS): PTC probe are monitored while the motor power supply is connected
FLt- [FAULT MANAGEMENT] (continued)
rSt- [FAULT RESET]
rSF [Fault reset]
[No] (nO)
nO
LI1
...
Detected faults are cleared manually when the assigned input or bit changes to 1, if the cause of the detected fault has
disappeared.
The STOP/RESET key on the graphic display terminal performs the same function.
Following detected faults can be cleared manually : ASF, brF, bLF, CnF, COF, dLF, EPF1, EPF2, FbES ,
FCF2, InF9, InFA, InFb, LCF, LFF3, ObF, OHF, OLC, OLF, OPF1, OPF2, OSF, OtFL, PHF,
PtFL, SCF4, SCF5, SLF1, SLF2, SLF3, SOF, SPF, SSF, tJF, tnF and ULF.
[No] (nO): Function inactive
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
DRI- > CONF > FULL > FLT-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com