Installation manual

Configuration Mode (ConF)
236 S1A28692 03/2010
Motor thermal protection
Function
Thermal protection by calculating the I²t.
Note: The motor thermal state is not saved when the drive is switched off.
Self-cooled motors: The tripping curves depend on the motor frequency.
Force-cooled motors: Only the 50 Hz tripping curve needs to be considered, regardless of the motor
frequency.
The following curves represent the trip time in seconds:.
10, 000
1, 000
100
0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6
50 Hz20 Hz10 Hz
1 Hz
3 Hz
5 Hz
Trip time in seconds
Motor current / ItH
CAUTION
RISK OF DAMAGE TO THE MOTOR
External protection against overloads is required under the following circumstances:
When the product is being switched on again, as there is no memory to record the motor thermal state
When supplying more than one motor
When supplying motors with ratings less than 0.2 times the nominal drive current
When using motor switching
Failure to follow these instructions can result in equipment damage.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com