Installation manual

Configuration Mode (ConF)
238 S1A28692 03/2010
Parameters described in this page can be accessed by:
FLt- [FAULT MANAGEMENT] (continued)
OPL- [OUTPUT PHASE LOSS]
OPL [Output Phase Loss]
[Yes] (YES)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If [Output phase loss] (OPL) is set to [No] (nO) or [Output cut] (OAC), loss of cable is not detected.
Check this action will not endanger personnel or equipment in any way.
Failure to follow these instructions will result in death or serious injury.
nO
YES
OAC
Note: [Output phase loss] (OPL) is set to [No] (nO) when [Motor control type] (Ctt) page 92
is set to
[Sync. mot.] (SYn). For other [Motor control type] (Ctt) configurations, [Output phase loss] (OPL) is forced to [Yes]
(YES) if brake logic control is configured.
[No] (nO): Function inactive
[Yes] (YES): Tripping on [Output phase loss] (OPL) with freewheel stop
[Output cut] (OAC): No fault triggered, but management of the output voltage in order to avoid an overcurrent when the link
with the motor is re-established and catch on the fly performed (even if this function has not been configured).
The drive switches to [Output cut] (SOC) state after [OutPh time detect] (Odt) time. Catch on fly is possible as soon as the
drive is in Stand by output cut [Output cut] (SOC) state.
Odt [OutPh time detect]
0.5 to 10 s 0.5 s
T
Time delay for taking the [Output Phase Loss] (OPL) detected fault into account.
FLt- [FAULT MANAGEMENT] (continued)
IPL- [INPUT PHASE LOSS]
IPL [Input phase loss]
According to drive rating
g
Cannot be accessed if drive rating is ATVpppM2.
In this case, no factory settings value.
Factory setting : [Freewheel] (YES) for drive rating ATV32pppN4.
If 1 phase disappears and if this leads to performance decrease, the drive switches to fault mode [Input phase loss] (PFH).
If 2 or 3 phases disappear, the drive trips in [Input phase loss] (PFH).
nO
YES
[Ignore] (nO): Detected fault ignored
[Freewheel] (YES): Detected fault with freewheel stop
Code Name / Description Adjustment range Factory setting
2 s
2 s
DRI- > CONF > FULL > FLT- > OPL-