Installation manual

Configuration Mode (ConF)
240 S1A28692 03/2010
Parameters described in this page can be accessed by:
Deferred stop on thermal alarm
This function helps to prevent the drive stopping between two steps of the process if the drive or motor
overheats, by authorizing operation until the next stop. At the next stop, the drive is locked until the thermal
state falls back to a value, which undershoots the set threshold by 20%. Example: A trip threshold set at 80%
enables reactivation at 60%.
One thermal state threshold must be defined for the drive, and one thermal state threshold for the motor(s),
which will trip the deferred stop.
Code Name / Description Adjustment range Factory setting
FLt- [FAULT MANAGEMENT] (continued)
SAt- [THERMAL ALARM STOP]
SAt [Thermal alarm stop]
[No] (nO)
nO
YES
Thermal alarm stop function allow to set a custom alarm thermal level for the drive or the motor. When one of these levels is
reached, the drive trips in freewheel stop.
[No] (nO): Function inactive (in this case, the following parameters cannot be accessed)
[Yes] (YES): Freewheel stop on drive or motor thermal alarm
tHA
T
[Drv therm. state al]
0 to 118% 100%
Thermal state threshold of the drive tripping the deferred stop.
ttd
T
[Motor therm. level]
0 to 118% 100%
Thermal state threshold of the motor tripping the deferred stop.
ttd2
T
[Motor2 therm. level]
0 to 118% 100%
Thermal state threshold of the motor 2 tripping the deferred stop.
ttd3
T
[Motor3 therm. level]
0 to 118% 100%
Thermal state threshold of the motor 3 tripping the deferred stop.
FLt- [FAULT MANAGEMENT] (continued)
EtF- [EXTERNAL FAULT]
EtF [External fault ass.]
[No] (nO)
nO
LI1
...
If the assigned bit is at 0, there is no external fault.
If the assigned bit is at 1, there is an external fault.
Logic can be configured via [External fault config] (LEt) if a logic input has been assigned.
[No] (nO):
Function inactive
[LI1] (LI1): Logical input LI1
[...] (...): See the assignment conditions on page 138
LEt [External fault config]
[Active high] (HIG)
g
Parameter can be accessed if the external fault has been assigned to a logic input. It defines the positive or negative logic of
the input assigned to the detected fault.
LO
HIG
[Active low] (LO): Trip on falling edge (change from 1 to 0) of the assigned input
[Active high] (HIG): Trip on rising edge (change from 0 to 1) of the assigned input
DRI- > CONF > FULL > FLT- > SAT-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com