Installation manual

Interface (ItF)
S1A28692 03/2010 267
Parameters described in this page can be accessed by:
Monitor screen type
Code Name / Description Factory setting
MSC- [MONITOR SCREEN TYPE]
Mdt [Display value type]
[Digital] (dEC)
T
[Digital] (dEC)
[Bar graph] (bAr)
[List] (LISt)
MPC
[PARAMETER SELECTION]
g
[AI1]
[AI2]
[AI3]
[AO1]
[ETA state world]
[Alarm groups]
[Frequency ref.]
[Output frequency]
[Pulse in. work. freq.]
[Motor current]
[Motor speed]
[Motor voltage]
[Motor power]
[Motor torque]
[Mains voltage]
[Motor thermal state]
[Drv. thermal state]
[Consumption]
[Run time]
[Power on time]
[IGBT alarm counter]
[Min. freq time]
[PID reference]
[PID feedback]
[PID error]
[PID Output]
in V
in V
in mA
in V
in Hz: parameter displayed in factory configuration
in Hz
in A: parameter displayed in factory configuration
in Hz
in rpm
in V
in W
as a %
in V
as a %
as a %
in Wh or kWh depending on drive rating
in hours (length of time the motor has been switched on)
in hours (length of time the drive has been switched on)
in seconds (total time of IGBT overheating alarms)
in seconds
as a %
as a %
as a %
in Hz
Select the parameter(s) using ENT (a then appears next to the parameter). Parameter(s) can also be deselected using ENT.
Examples include:
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
PARAMETER SELECTION
MONITORING
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
- - - - - - - - -
Display of 2 digital values Display of 2 bar graphs Display of a list of 5 values
RUN Term +35.0 Hz 80.0 A RUN Term +35.0 Hz 80.0 A RUN Term +35.0 Hz 80.0 A
Motor speed Min Motor speed max 1.2 MONITORING
1250 rpm
0 1250 rpm 1500 Frequency ref. : 50.1Hz
Motor current: 80 A
Motor current Min Motor current max Motor speed: 1250 rpm
80 A
0 80 A 150 Motor thermal state: 80%
Drv thermal state : 80%
Quick Quick Quick
ITF- > MCF- > MSC-