Installation manual

Diagnostics and Troubleshooting
294 S1A28692 03/2010
OPF2
[3 motor phase loss]
Motor not connected or motor power
too low.
Output contactor open.
Instantaneous instability in the motor
current.
Check the connections from the drive to the motor.
If an output contactor is being used, set
[Output Phase Loss] (OPL) to [Output cut] (OAC), page
238
.
Test on a low power motor or without a motor: In factory
settings mode, motor phase loss detection is active
[Output Phase Loss] (OPL) = [Yes] (YES). To check the
drive in a test or maintenance environment, without having to
use a motor with the same rating as the drive (in particular for
high power drives), deactivate motor phase loss detection
[Output Phase Loss] (OPL) = [No] (nO), see instructions
given page 238
.
Check and optimize the following parameters:
[IR compensation] (UFr ) page 78
, [Rated motor volt.]
(UnS) and [Rated mot. current] (nCr) page 74
and
perform [Auto tuning] (tUn) page 75
.
OSF
[Mains overvoltage]
Line voltage too high.
Disturbed mains supply.
Check the line voltage.
OtFL
[LI6=PTC overheat]
Overheating of PTC probes detected
on input LI6.
Check the motor load and motor size.
Check the motor ventilation.
Wait for the motor to cool before restarting.
Check the type and state of the PTC probes.
PtFL
[LI6=PTC probe]
PTC probe on input LI6 open or
short-circuited.
Check the PTC probe and the wiring between it and the
motor/drive.
SCF4
[IGBT short circuit]
Power component detected fault. Contact Schneider Electric Product Support.
SCF5
[Motor short circuit]
Short-circuit at drive output. Check the cables connecting the drive to the motor, and the
motor’s insulation.
Contact Schneider Electric Product Support.
SLF1
[Modbus com.]
Communication interruption on the
Modbus bus.
Check the communication bus.
Check the time-out.
Refer to the Modbus User's manual.
SLF2
[PC com.]
Communication interruption with PC
Software.
Check the PC Software connecting cable.
Check the time-out.
SLF3
[HMI com.]
Communication interruption with the
graphic display terminal or remote
display terminal.
Check the terminal connection
Check the time-out.
SSF
[Torque/current lim]
Switch to torque or current limitation. Check if there are any mechanical problems.
Check the parameters of [TORQUE LIMITATION] (tOL-)
page 202
and the parameters of the
[TORQUE OR I LIM. DETECT.] (tId-), page 245
.
tJF
[IGBT overheat]
Drive overheated. Check the size of the load/motor/drive.
Reduce the switching frequency.
Wait for the motor to cool before restarting.
ULF
[Proc. underload Flt]
Process underload. Check and remove the cause of the underload.
Check the parameters of the
[PROCESS UNDERLOAD] (Uld-) function, page 251
.
Detected Fault Name Probable cause Remedy