Installation manual

Monitoring Mode (MOn)
46 S1A28692 03/2010
Parameters described in this page can be accessed by:
AIA- [ANALOG INPUTS IMAGE]
Analog input functions.
AI1C
[AI1]
V
AI1 customer image: Value of analog input 1.
AI1A [AI1 assignment]
nO
Fr1
Fr2
SA2
PIF
tAA
dA2
PIM
FPI
SA3
Fr1b
dA3
FLOC
MA2
MA3
PES
IA01
...
IA10
AI1 functions assignment. If no functions have been assigned, [No] (nO) is displayed.
Following parameters are visible on the graphic display terminal by pressing the ENT key on the parameter.
[No] (nO): Not assigned
[Ref.1 channel] (Fr1): Reference source 1
[Ref.2 channel] (Fr2): Reference source 2
[Summing ref. 2] (SA2): Summing reference 2
[PID feedback] (PIF): PI feedback (PI control)
[Torque limitation] (tAA): Torque limitation: Activation by an analog value
[Subtract. ref. 2] (dA2): Subtracting reference 2
[Manual PID ref.] (PIM ): Manual speed reference of the PI(D) regulator (auto-man)
[PID speed ref.] (FPI): Speed reference of the PI(D) regulator (predictive reference)
[Summing ref. 3] (SA3): Summing reference 3
[Ref.1B channel] (Fr1b): Reference source 1B
[Subtract. ref. 3] (
dA3): Subtr
acting reference 3
[Forced local] (FLOC): Forced local reference source
[Ref. 2 multiplier] (MA2): Multiplying reference 2
[Ref. 3 multiplier] (MA3): Multiplying reference 3
[Weight input] (PES): External weight measurement function
[IA01] (IA01): Functions blocks: Analog Input 01
...
[IA10] (IA10): Functions blocks: Analog Input 10
UIL1 [AI1 min value]
V
Voltage scaling parameter of 0%.
UIH1 [AI1 max value]
V
Voltage scaling parameter of 100%.
AI1F [AI1 filter]
s
Interference filtering cut-off time of the low-filter.
AlA- [ANALOG INPUTS IMAGE] (continued)
Analog input functions.
AI2C
[AI2]
V
AI2 customer image: Value of analog input 2.
AI2A [AI2 assignment]
AI2 functions assignment. If no functions have been assigned, [No] (nO) is displayed.
Following parameters are visible on the graphic display terminal by pressing the ENT key on the parameter.
Identical to [AI1 assignment] (AI1A) page 46
.
UIL2 [AI2 min value]
V
Voltage scaling parameter of 0%.
UIH2 [AI2 max value]
V
Voltage scaling parameter of 100%.
AI2F [AI2 filter]
s
Interference filtering cutoff time of the low-filter.
Code Name / Description Unit
DRI- > MON- > IOM- > AIA-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com