Installation manual

Monitoring Mode (MOn)
S1A28692 03/2010 49
Parameters described in this page can be accessed by:
SFFE [Safety fault reg.]
Safety function detected fault error register.
Bit 0 = 1: Logical Input debounce time out
Bit 1: Reserved
Bit 2 = 1: Motor speed sign changed during SS1 stop
Bit 3 = 1: Motor speed reached SS1 trip area
Bit 4: Reserved
Bit 5: Reserved
Bit 6 = 1: Motor speed sign changed during SLS Safe Limitation
Bit 7 = 1: Motor speed reached SLS trip area
Bit 8: Reserved
Bit 9: Reserved
Bit 10: Reserved
Bit 11: Reserved
Bit 12: Reserved
Bit 13 = 1: Motor speed measurement is not possible
Bit 14 = 1: Motor ground short circuit detected
Bit 15 = 1: Motor phase to phase short circuit detected
MOn- [1.2 MONITORING] (continued)
MFb- [MONIT. FUN. BLOCKS]
For more details on Function Blocks, please refer to dedicated Function Blocks manual.
FbSt
IdLE
CHEC
StOP
InIt
rUn
Err
[FB status]
Function Block Status.
[Idle] (IdLE): Idle state
[Check prog.] (CHEC): Check program state
[Stop] (StOP): STOP state
[Init] (InIt): Initialization state
[Run] (rUn): RUN state
[Err] (Err): Error state
FbFt
nO
Int
bIn
InP
PAr
CAL
tOAU
tOPP
AdL
In
[FB fault]
Status of the function blocks execution.
[No] (nO): No fault detected
[Internal] (Int): Internal fault detected
[Binary file] (bIn): Binary fault detected
[Intern para.] (InP): Internal parameter fault detected
[Para. RW] (PAr): Parameter access fault detected
[Calculation] (CAL): Calculation fault detected
[TO AUX] (tOAU): TimeOut AUX task
[TO synch] (tOPP): TimeOut in PRE/POST task
[Bad ADLC] (AdL): ADLC with bad parameter
[Input assign.] (In): Input not configured
FbI- [FB IDENTIFICATION]
bUEr [Program version]
g
Program user version. Can be accessed if [FB status] (FbSt) is not set to [Idle] (IdLE).
bnS
g
[Program size]
Program file size. Can be accessed if [FB status] (FbSt) is not set to [Idle] (IdLE).
bnU [Prg. format version]
Binary format version of the drive. Can be accessed if [FB status] (FbSt) is not set to [Idle] (IdLE).
CtU [Catalogue version]
Catalog version of the drive.
Code Name / Description Unit
DRI- > MON- > SAF-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com