Installation manual

Monitoring Mode (MOn)
S1A28692 03/2010 59
Parameters described in this page can be accessed by:
InF9
InFA
InFb
InFE
LCF
LFF3
ObF
OCF
OHF
OLC
OLF
OPF1
OPF2
OSF
OtFL
PHF
PtFL
SAFF
SCF1
SCF3
SCF4
SCF5
SLF1
SLF2
SLF3
SOF
SPF
SrF
SSF
tJF
tnF
ULF
USF
[Internal- I measure] (InF9): Current measurement circuit detected error
[Internal-mains circuit] (InFA): Input phase loss circuit detected error
[Internal- th. sensor] (InFb): Thermal sensor detected error (OC or SC)
[Internal-CPU] (InFE): CPU detected fault (ram, flash, task ...)
[Input contactor] (LCF): Line contactor detected error
[AI3 4-20mA loss] (LFF3): AI3 4-20 mA loss
[Overbraking] (ObF): Overbraking
[Overcurrent] (OCF): Overcurrent
[Drive overheat] (OHF): Drive overheating
[Proc.Overload Flt] (OLC): Torque overload
[Motor overload] (OLF): Motor overload
[1 output phase loss] (OPF1): Motor 1-phase loss
[3out ph loss]
(OPF2): Motor
3-phases loss
[Mains overvoltage] (OSF): Oversupply detected fault
[PTC fault] (OtFL): Motor overheating detected error from PTCL: standard product
[Input phase loss] (PHF): Main input 1-phase loss
[LI6=PTC probe] (PtFL): PTCL detected error (OC or SC)
[Safety fault] (SAFF): Safety function trip
[Motor short circuit] (SCF1): Motor short circuit (hard detection)
[Ground short circuit] (SCF3): Direct ground short-circuit trip (hard detection)
[IGBT short circuit] (SCF4): IGBT short-circuit (hard detection)
[Motor short circuit] (SCF5): Load short-circuit during Igon load sequence (hard detection)
[Modbus com.] (SLF1): Modbus local serial communication interruption
[PC com.] (SLF2): PC Software communication interruption
[HMI com.] (SLF3): Remote terminal communication interruption
[Overspeed] (SOF): Overspeed
[Speed fdback loss] (SPF): Speed feedback loss
[Torque time-out] (SrF): Torque regulation time-out
[Torque/current lim] (SSF): Torque current limitation detected fault
[IGBT overheat] (tJF)
: IGBT overheating
[A
uto-tuning] (tnF): Tune detected fault
[Pr.Underload Flt] (ULF): Torque underload
[Undervoltage] (USF): Undervoltage
HS1 [Drive state]
tUn
dCb
rdY
nSt
rUn
ACC
dEC
CLI
FSt
FLU
nLP
CtL
Obr
SOC
USA
tC
St
FA
YES
EP
FLt
SS1
SLS
StO
HMI Status of the detected fault record 1.
[Auto-tuning] (tUn): Auto-tuning
[In DC inject.] (dCb): Injection braking
[Ready] (rdY): Drive ready
[Freewheel] (nSt): Freewheel stop control
[Drv running] (rUn): Motor in steady state or run command present and zero reference
[In accel.] (ACC): Acceleration
[In decel.] (dEC): Deceleration
[Current lim.] (CLI): Current limit
[Fast stop] (FSt): Fast stop
[Mot. fluxing] (FLU): Fluxing function is activated
[no mains V.] (nLP): Control is powered on but the DC bus is not loaded
[control.stop] (CtL): Controlled stop
[Dec. adapt.] (Obr): Adapted deceleration
[Output cut] (SOC): Stand by output cut
[UnderV. al.] (US
A): Undervoltage alarm
[In mfg. test] (tC): TC indus mode activated
[in autotest] (St): Self test in progress
[autotest err] (FA): Self test detected error
[Autotest OK] (YES): Self test OK
[eeprom test] (EP): Self test Eeprom detected error
[In fault] (FLt): Product has detected a fault
[SS1 active] (SS1): Safety SS1 level
[SLS active] (SLS): Safety SLS level
[STO active] (StO): Safety STO level
Ep1 [ETA state word]
DRIVECOM status register of detected fault record 1 (same as [ETA state word] (EtA) page 51).
IP1 [ETI state word]
Extended status register of detected fault record 1 (see the communication parameters file).
Code Name / Description Unit
DRI- > MON- > DGT- > PFH-