Configuration Mode (ConF)
74 S1A28692 03/2010
Parameters described in this page can be accessed by:
CCFG [Customized macro]
g
Read-only parameter, only visible if at least one macro configuration parameter has been modified.
nO
YES
[No] (nO): No
[Yes] (YES): Yes
bFr [Standard mot. freq]
[50Hz IEC] (50)
50
60
This parameter modifies the presets of the following parameters: [Rated motor volt.] (UnS) below, [High speed] (HSP) page
75
, [Freq. threshold] (Ftd) page 89, [Rated motor freq.] (FrS) and [Max frequency] (tFr) .
[50Hz IEC] (50): Drive 50 Hz
[60Hz NEMA] (60): Drive 60 Hz
IPL [Input phase loss]
Yes or No, according to drive
rating
g
This parameter is only accessible in this menu on 3-phases drives.
If one phase disappears, the drive switches to fault mode [Input phase loss] (PFH), but if 2 or 3 phases disappear, the drive
continues to operate until it trips on an undervoltage detected fault (the drive trips in [Input phase loss] (PHF) if there is an
input phase loss and if this leads to performance decrease).
See [Input phase loss] (IPL) page 238
.
nO
YES
[Ignore] (nO): Detected fault ignored, to be used when the drive is supplied via a single-phase supply or by the DC bus
[Freewheel] (YES): With freewheel stop
nPr [Rated motor power]
According to drive rating
g
Rated motor power given on the nameplate, in kW if [Standard mot. freq] (bFr) is set to [50Hz IEC] (50), in HP if
[Standard mot. freq] (bFr) is set to [60Hz NEMA] (60).
See [Rated motor power] (nPr) page 94
.
UnS [Rated motor volt.]
100 to 480 V According to drive rating
g
Rated motor voltage given on the nameplate.
ATV32pppM2: 100 to 240 V – ATV32pppN4: 200 to 480 V.
See [Rated motor volt.] (UnS) page 94
.
nCr [Rated mot. current]
0.25 to 1.5 In (1) According to drive rating and
[Standard mot. freq] (bFr)
g
Rated motor current given on the nameplate.
See [Rated mot. current] (nCr) page 94
.
FrS [Rated motor freq.]
10 to 599 Hz 50 Hz
g
Rated motor frequency given on the nameplate.
The factory setting is 50 Hz, or preset to 60 Hz if [Standard mot. freq] (bFr) is set to 60 Hz.
This parameter is not visible if [Motor control type] (Ctt) page 92
is set to [Sync. mot.] (SYn).
See [Rated motor freq.] (FrS) page 94
.
nSP [Rated motor speed]
0 to 65,535 rpm According to drive rating
g
Rated motor speed given on the nameplate.
This parameter is not visible if [Motor control type] (Ctt) page 92
is set to [Sync. mot.] (SYn).
See [Rated motor speed] (nSP) page 94
.
0 to 9,999 rpm then 10.00 to 60.00 krpm on the integrated display terminal.
If, rather than the rated speed, the nameplate indicates the synchronous speed and the slip in Hz or as a %, calculate the rated
speed as follows:
Nominal speed = Synchronous speed x
or
Nominal speed = Synchronous speed x (50 Hz motors)
or
Nominal speed = Synchronous speed x (60 Hz motors)
Code Name / Description Adjustment range Factory setting
100 - slip as a %
100
50 - slip in Hz
50
60 - slip in Hz
60
DRI- > CONF > FULL > SIM-