Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 79
Parameter settings for [K speed loop filter] (SFC), [Speed prop. gain] (SPG) and [Speed time integral] (SIt)
The following parameters can be accessed if [Motor control type] (Ctt) page 92 is set to [SVC V] (UUC),
[Sync. mot.] (SYn) or [Energy Sav.] (nLd).
General Case: Setting for [K speed loop filter] (SFC) = 0
The regulator is an "IP" type with filtering of the speed reference, for applications requiring flexibility and
stability (hoisting or high inertia, for example).
[Speed prop. gain] (SPG) affects excessive speed.
[Speed time integral] (SIt) affects the passband and response time.
WARNING
LOSS OF CONTROL
Bad parameter settings of the speed loop with High Inertia application may cause a Ramp non consistent
with application.
Failure to follow these instructions will result in death, serious injury, or equipment damage.
Initial response
Reduction in SIT Reduction in SIT
Initial response
Increase in SPG Increase in SPG
0 50045040035030025020015010050
0
1
0.8
0.6
0.4
0.2
Reference division
Time in ms
0 50045040035030025020015010050
0
1
0.8
0.6
0.4
0.2
Reference division
Time in ms
0 50045040035030025020015010050
0
1
0.8
0.6
0.4
0.2
Reference division
Time in ms
0 50045040035030025020015010050
0
1
0.8
0.6
0.4
0.2
Reference division
Time in ms
0 50045040035030025020015010050
0
1
0.8
0.6
0.4
0.2
Reference division
Time in ms
0 50045040035030025020015010050
0
1
0.8
0.6
0.4
0.2
Reference division
Time in ms
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com