Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 89
Parameters described in this page can be accessed by:
tLIM [Motoring torque lim]
0 to 300% 100%
g
T
Torque limitation in motor mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque increment] (IntP) parameter, page 202
.
See page 202
.
tLIG [Gen. torque lim]
0 to 300% 100%
g
T
Torque limitation in generator mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque increment] (IntP) parameter, page 202
.
See page 202
.
trH [Traverse freq. high]
0 to 10 Hz 4 Hz
g
T
Traverse high. See page 227.
trL [Traverse freq. low]
0 to 10 Hz 4 Hz
g
T
Traverse low. See page 227.
qSH [Quick step High]
0 to [Traverse freq. high] (trH) 0 Hz
g
T
Quick step high. See page 227.
qSL [Quick step Low]
0 to [Traverse freq. low] (trL 0 Hz
g
T
Quick step low. See page 227.
Ctd [Current threshold]
0 to 1.5 In (1) In (1)
T
Current threshold for [I attained] (CtA) function assigned to a relay or a logic output (see page 123). See page 234.
ttH [High torque thd.]
-300% to +300% 100%
T
High torque threshold for [High tq. att.] (ttHA) function assigned to a relay or a logic output (see page 123), as a % of the
rated motor torque. See page 234
.
ttL [Low torque thd.]
-300% to +300% 50%
T
Low torque threshold for [Low tq. att.] (ttLA) function assigned to a relay or a logic output (see page 123), as a % of the rated
motor torque. See page 234
.
FqL [Pulse warning thd.]
0 Hz to 20,000 kHz 0 Hz
g
Speed threshold measured by the [FREQUENCY METER] (FqF-) function, page 247, assigned to a relay or a logic output
(see page 123
). See page 235.
Ftd [Freq. threshold]
0.0 to 599 Hz HSP
T
Motor frequency threshold for [Freq.Th.att.] (FtA) function assigned to a relay or a logic output (see page 123), or used by the
[PARAM. SET SWITCHING] (MLP-) function, page 215
. See page 234.
F2d [Freq. threshold 2]
0.0 to 599 Hz HSP
T
Motor frequency threshold for [Freq. Th. 2 attain.] (F2A) function assigned to a relay or a logic output (see page 123), or used
by the [PARAM. SET SWITCHING] (MLP-) function, page 215
. See page 234.
FFt [Freewheel stop Thd]
0.2 to 599 Hz 0.2 Hz
g
T
Speed threshold below which the motor will switch to freewheel stop.
This parameter supports switching from a ramp stop or a fast stop to a freewheel stop below a low speed threshold.
It can be accessed if [Type of stop] (Stt) is set to [Fast stop] (FSt) or [Ramp stop] (rMP) and if [Brake assignment]
(bLC) or [Auto DC injection] (AdC) are configured. See page 158
.
Code Name / Description Adjustment range Factory setting
DRI- > CONF > FULL > SET-