Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 93
Parameters described in this page can be accessed by:
UF5
SYn
UFq
nLd
[V/F 5pts] (UF5): 5-segment V/F profile: As [Standard] (Std) profile but also supports the avoidance of resonance
(saturation).
Note: U0 is the result of an internal calculation based on motor parameters and multiplied by UFr (%). U0 can be adjusted by
modifying UFr value.
[Sync. mot.] (SYn): For synchronous permanent magnet motors with sinusoidal electromotive force (EMF) only. This selection
makes the asynchronous motor parameters inaccessible, and the synchronous motor parameters accessible.
[V/F Quad.] (UFq): Variable torque. For pump and fan applications.
[Energy Sav.] (nLd): Energy saving. For applications that do not require high dynamics.
Code Name / Description Adjustment range Factory setting
Voltage
Frequency
FrS
UnS
U5
U4
U3
U1
U2
U0
F1 F2
F3
F4
F5
FrS > F5 > F4 > F3 > F2 > F1
The profile is defined by the
values of parameters UnS, FrS,
U1 to U5 and F1 to F5.
DRI- > CONF > FULL > DRC-