User`s manual

Software Configuration Examples
02/2005 49
2 Check the Profibus slave address in SyCon and the number of words. The
number of bytes must be equal, or lower in the SyCon than configured in the
ABC configuration tool. Here in the ABC tool 40 Input Bytes and 2 Output Bytes
are provided = > in SyCon 40 / 2 = 20 input words and 2 / 2 = 1 output word in
maximum.
SyCon / ABC check:
3 Check that the SyCon address and hardware address of the gateway are equal.
In our example, the gateway address is 73!
Hardware address and SyCon address:
Step Action
Number of bytes must be equal
put in 73 as station address