Installation manual

www.schneider-electric.com
BBV48787
Introduction
DANGER
Important information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or
simplifies a procedure
PLEASE NOTE
The word "drive" as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility
is assumed by Schneider Electric for any consequences arising out of the use of this product.
© 2009 Schneider Electric. All Rights Reserved
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
Before you begin
Read and understand these instructions before performing any procedure with this product
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the Multi-loader.
• Any changes made to a device using the Multi-loader must be performed by qualified personnel.
• Read and understand the device manuals before you load or duplicate the Configuration from one device to another device.
• Ensure that you select the Configuration suitable for your application
Failure to follow these instructions will result in death or serious injury.
DANGER
Setup procedure
2. Connect the Multi-Loader
v To a PC. (see page6)
v To a device.(see page 7)
v Load a configuration onto the Multi-Loader. (see page 9)
v Transfer a configuration to a device. (see page 10)
v Transfer a configuration to several devices : Quick
Store (see page 11)
1. Receive and inspect the Multi-Loader
Check that the reference printed on the label is the same as that on the
purchase order.
Remove the Multi-Loader from its packaging and check that it has not
been damaged in transit.
The Multi-Loader is a standalone tool for transferring configuration files to devices with their power on or off.
The Multi-Loader is used to set device parameters by loading a configuration file onto the device(s). (Devices must have the same
reference. A consistency check is performed before the data transfer). On some devices the parameters can be set with them still in
their box or before they are powered up.
- This portable tool has been designed to load up to fifty devices a day and has a battery life of six days. However, this depends
on the transfer time, the size of the configuration files and other parameters associated with the settings for the Multi-Loader and
the connected devices.
- It can configure ten drives in less than five minutes.
- The Multi-Loader can provide the power supply for certain devices if they are turned off during the transfer.
The Multi-Loader is also a firmware update tool.
-The "Password FW" mode can be used to protect against incorrect operation by means of a password.
All representations of the ATV12 drive throughout this document are given by way of example only to symbolize a device. Please refer to
the device compatibility tables on page 8.
A) The device's configuration file is
copi
ed to
the
Mul
ti-Loader's SD card. (See page 9)
B) The configuration file is generated by SoMove then transferred to the Multi-Loader's SD card.
1) The user selects and then transfers the configuration file from the Multi-Loader to the device. (See page 10)
2) Once the initial transfer is complete, the user can use Quick Store mode, which allows the Multi-Loader to load the same update file
on several devices in succession. (See page 11)
Duplicating or generating configuration files
A) Configuration duplicated
B) Configuration generated
2) Transfer to several
1) Transfer to one device
SoMove
devices using Quick Store
Product reference:
Check that the product reference printed on the label is the same as that on the delivery note. This should also correspond with the number
on the purchase order.
Contents of the Multi-Loader box (VW3A8121)
Check that the Multi-Loader box contains the following:
1 x Multi-Loader
4 x LR6 (AA) batteries
1 x SD card
1 x Standard USB type A to Mini-B cable
1 x RJ45 (RJ45/RJ45) cable
1 x RJ45 female/female adapter (VW3A1105)
1 x Carry case
1 x Simplified manual (English and French)
1 x Impact resistant cover
Available as an option
Multi-Loader Cordset (VW3A8126)
Receipt of the Multi-Loader
Presentation
Weight
250 grams (including batteries)
Data storage
One SD card is supplied with the Multi-Loader. Any standard SD card is compatible with the tool.
Language
The menus are in English.
Power supplies
Two options are available for powering the Multi-Loader:
4 x LR6 (AA) alkaline batteries (batteries included)
NiMh rechargeable batteries (batteries and charger not included)
Battery life
Depending on the type of batteries used, the Multi-Loader can transfer up to 300 configuration files.
Power save feature
To prolong battery life, a standby function is activated within a programmable time delay; the Multi-Loader is reactivated by pressing the
ON/OFF button.
Connection to a powered-up PC or device can also help conserve battery power, as the power supply from the connected device takes over
from the batteries.
Receipt of the Multi-Loader
Description
RJ 45 connector
The connection between the Multi-Loader and the device is via a RJ45
cable to load and transfer configuration files or updated application
RJ11 connector with label cover
This connector is reserved for Schneider Electric product support.
SD card slot
The SD card receives and stores the files. One SD card is supplied with
the Multi-Loader.
Battery compartment
The Multi-Loader can take normal batteries or rechargeable batteries.
ON/OFF button
Press for 2 seconds to turn the tool on or off.
Quick Store key
Press this key to transfer data from the Multi-Loader to the device after
an initial transfer.
Screen
The screen comprises 2 lines of 16 characters.
ESC key
Returns to the previous screen.
ENT key
Confirms the parameter selection or cancels messages.
Up arrow key
For menu navigation.
Down arrow key
For menu navigation.
Letter Description Comments
A
B
C
D
E
F
G
H
I
J
K
L
Mini-B USB connector
The connection between the Multi-Loader (USB Mini-B type) and the PC
(USB type A) is via a 1 m (3.28 feet) USB type A to Mini-B cable.
Connecting the Multi-Loader
This section describes the various ways of connecting the Multi-Loader.
Connection to a PC
There are two ways of storing files on the SD card:
- Insert the SD card in the Multi-Loader and connect the Multi-Loader to the PC via the standard USB type A to Mini-B cable (see
Figure 3 below)
OR
- Insert the SD card in the SD card reader on the PC (see Figure 4 below)
For both these methods, the SD card is recognized as an external storage device; no driver is required. The SD card operates in Windows
Explorer using the same copy/paste actions as any standard external storage medium.
Note :
The PC must be on and operational before connecting the Multi-Loader to avoid
The SD card must not be removed when the Multi-Loader is on and a transfer is in progress. Otherwise, data on the SD card may be
lost.
The following priority rules come into play when the Multi-Loader is connected to a PC:
- If no transfer is in progress between the Multi-Loader and the drive, the connection to the drive is ignored and the Multi-Loader is
detected by the PC.
- If a transfer is in progress between the Multi-Loader and the drive, the user must wait until the transfer is complete. The Multi-
Loader must then be reconnected so the PC can detect it.
Source of configuration files
There are two ways of managing configuration files:
- If a device's configuration is to be duplicated, it is copied to another device via the Multi-Loader. See "Loading a configuration
from device" on page 9 and "Configuration transfers" on page 10 and 11.
- If the configuration file is generated by SoMove software, it must then be transferred to the Multi-Loader's SD card. See
"Downloads" on page 15 and "Connection to a PC" above.
A: USB type A connector B: USB Mini-B type connector
SD card reader
Figure 3 Figure 4
Connecting the Multi-Loader
Connection to a drive
There are three ways of transferring configuration files.
When the drive is off, the Multi-Loader is powered by its batteries.
Note: When the drive is in its box, the guiding tool option can be used for quicker and easier in-box connection (no locking tab on the
connector), thus speeding up the transfer and keeping the packaging intact.
When the drive is on, the Multi-Loader is powered by the drive via the RJ45 cable.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH - EXPOSURE TO ENERGIZED PARTS
• Adhere to NFPA 70E guidelines when using the Multi-Loader.
• The Multi-Loader is to be used only by qualified personnel as defined in NFPA 70E
• Read and understand the manuals for the applicative drive before accessing the communication port of the drive.
• Ensure that the RJ45 cable is not damaged
Failure to follow these instructions will result in death or serious injury.
The drive is in its packaging
The drive is mounted, wired, and powered-up
or
the drive is power on
v Presentation. (see page 4)
v Description. (see page 5)
3. Duplicate device configurations
4. Multi-Loader main menu (see page 12)
5. Diagnostic (see page 13)
For complete documentation, refer to www.schneider-electric.com
to avoid an incorrect start up of the PC.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before using the Multi-Loader. Operation of the Multi-Loader must be
performed by qualified personnel
• Read and understand the installation and programming manuals applicable to the drive that you are using with the
Multi-Loader. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with
respect to grounding the equipment.
• Many parts in this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across teminals PA/+ and PC/- or across the DC bus capacitors.
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
Schneider Electric recommends that all power from the drive and enclosures housing the drive is disconnected before performing this
procedure. If you choose not to follow this recommendation, you must adhere to NFPA 70E guidelines.
1. Remove all power from the drive and all enclosures housing the drive and wait 15 minutes to allow the DC bus of the drive to
discharge.
2. Insert the Multi-Loader's communication cable into the drive's RJ45 communication port. Refer to the drive's installation manual for
more information about how to perform this task.
3. Install and close all covers and doors before applying power to the drive. The drive must be powered on before performing an
upload or download.
4. Perform the desired transfer.
5. Upon completing the transfer, remove all power from the drive and the enclosures housing the drive and wait 15 minutes to allow
the DC bus of the drive to discharge.
6. Remove the Multi-Loader communication cable from the drive.
7. Install and close all covers and doors before reapplying power to the drive.
8. Confirm that the correct program is in the drive.
Multi-Loader