Installation manual

Specifications
A–2 152936
This manual is for use by qualified personnel only.
System Specifications
The Xantrex GT250 E has been designed for photovoltaic power systems, which
operate within the following specifications.
Environmental Specifications
CAUTION: Equipment Damage
Operation of the Xantrex GT250 E in a manner other than specified in this manual
may cause damage to the Xantrex GT250 E and other system components and
will void the terms of the warranty.
CAUTION
The Xantrex GT250 E will be destroyed if stored outside. Only store in dry areas.
Table A-1 Environmental Specifications
Specification Value
Dimensions 2112 mm H x 2006 mm W x 605 mm D
(83 in. H x 78 in. W x 24 in. D)
Weight 1160 kg (2557 lbs)
Allowable Ambient Temperature
Operating
Storage
-10 °C to 45 °C Maximum (14 °F to 113 °F)
-25 °C to 55 °C Maximum (-13 °F to 131 °F)
Relative Humidity EN60721 temperature 1K1 humidity 1K3
Elevation 1500 m
Storage Air Pressure 700 to 1060 mbar
Protection Class IP21
Cooling Air Power Element
1800 m
3
/h starting temperature 68 °C
Interior Cooling Air
2400 m
3
/h starting temperature 40/45 °C
Clearance (ventilation and
serviceability)
Top
Front
100 mm
600 mm (door clearance) plus local safety standards