Specifications

Installation
2–4 975-0298-01-01
Network terminators (Figure 2-2)—the Xantrex Xanbus network must
be properly terminated at each end with network terminators. If the
network is not properly terminated, signal quality is degraded and
performance on the network is reduced. Permanent configuration
without terminators is not supported by Schneider Electric.
One terminator is included with the Xantrex XW SCP. Depending on
your network layout, this terminator may need to be inserted into
another device elsewhere in the network.
Network Layout
Xantrex Xanbus-enabled devices are linked with separate lengths of
Xantrex Xanbus cable, as shown in Figure 2-3.
To ensure communication signal quality, each end of the network must
be terminated. The Xantrex Xanbus-enabled devices at each end of the
network must have a male terminator inserted into their open
network ports.
If the Xantrex XW SCP is the last device on the network, the open port on
the Xantrex XW SCP must be terminated.
Figure 2-2 Xantrex Xanbus Network Terminators
Figure 2-3 Daisy Chain Layout
System Control Panel II
Solar Charge Controller
Enter Exit
System Control Panel
Charge
Controller
Automatic Generator Start
Hybrid Inver ter/Charger
Gri d(A C1)
Gen (AC 2)
Fault /
Warning
Equalize
Battery
Char gi ng
Inverting
Flashing = sell
Inverter/Charger
Terminate the Xantrex Xanbus network at each end.