Specifications

Troubleshooting Reference
975-0298-01-01 5–3
W251 Please confirm:
Equalization
process.
Manual
You have
enabled
Equalization on
the inverter/
charger or
charge controller
menu.
Press Enter to
begin equalizing
batteries or Exit to
return to the
previous menu.
W252 Please confirm:
Restore default
settings.
Manual You have
selected the
Restore Defaults
command.
Press Enter to
restore default
settings or Exit to
cancel.
W254 The value failed
to change.
Try again.
Manual The setting you
are changing
can only be
changed when
the system is in
Standby mode.
Put the system in
Standby mode,
change the
setting, then
return the system
to Operating
mode.
W255 System clock
not set. Set
correct time.
Manual
On initial startup,
the clock needs
to be set. The
system will not
operate correctly
until it is.
Set the clock to
the correct time.
See “Using the
Clock Menu” on
page 3–12.
W256 A device is lost.
Check
connection.
Manual The Xantrex XW
SCP has lost
communications
with another
device on the
network.
Check network
connection
between the
Xantrex XW SCP
and the device.
W257 New device
detected.
Check device
settings.
Manual You have
connected a
new device to
the network or
reconnected a
disconnected
device.
Acknowledge the
message and
check that the
device is properly
configured.
Table 5-1 Warning Reference Table
Warning
number Message
Message
(translation) Type Cause Action