Conext XW series (120/240V)
Device short name XW+ 5548 NA XW+ 6848 NA
Inverter AC output
Output power (continuous) at 25°C 5500 W 6800 W
Overload 30 min / 60 sec at 25°C 7000 W / 9500 W 8500 W / 12000 W
Output power (continuous) at 40°C 4500 W 6000 W
Maximum output current 60 seconds (rms) 82 A (120 V); 41 A (240 V) 102 A (120 V); 52 A (240 V)
Output frequency (selectable) 50 / 60 Hz 50 / 60 Hz
Output voltage L-N: 120 V +/- 3%; L-L: 240 V +/- 3% L-N: 120 V +/- 3%; L-L: 240 V +/- 3%
Total harmonic distortion (THD) at rated power < 5% < 5%
Idle consumption search mode < 8 W < 8 W
Input DC voltage range 42 to 60 V (48 V Nominal) 42 to 60 V (48 V Nominal)
Maximum input DC current 150 A 180 A
Charger DC output
Maximum output charge current 110 A 140 A
Output voltage range 40 - 64 V (48 V Nominal) 40 - 64 V (48 V Nominal)
Charge control Three stage, two stage, boost, custom Three stage, two stage, boost, custom
Charge temperature compensation Battery temperature sensor included Battery temperature sensor included
Power factor corrected charging 0.98 0.98
Compatible battery types Flooded (default), Gel, AGM, LiON, custom* Flooded (default), Gel, AGM,LiON, custom*
Batter bank range (scaled to PV array size) 440 - 10000 Ah 440 - 10000 Ah
AC input
AC 1 (grid) input current (selectable limit) 3 - 60 A (60 A default) 3 - 60 A (60 A default)
AC 2 (generator) input current (selectable limit) 3 - 60 A (60 A default) 3 - 60 A (60 A default)
Automatic transfer relay rating / typical transfer time 60 A / 8 ms 60 A / 8 ms
AC input voltage limits (bypass/charge mode) L-N: 78 - 140 V (120 V nominal) L-N: 78 - 140 V (120 V nominal)
L-L: 160 - 270 V (240 V nominal) L-L: 160 - 270 V (240 V nominal)
AC input frequency range (bypass/charge mode) 55 - 65 Hz (default); 52 - 68 Hz (allowable) 55 - 65 Hz (default); 52 - 68 Hz (allowable)
AC grid-tie output
Grid sell current range on AC1(selectable limit) 0 to 40 A (120 V) / 0 to 20 A (240 V) 0 to 48 A (120 V) / 0 to 27 A (240 V)
Grid sell voltage range on AC1 L-N:105.5 to 132 +/- 1.5 V L-N:105.5 to 132 +/- 1.5 V
(auto adjusts entering sell mode) L-L: 211 to 264 +/- 3.0 V L-L: 211 to 264 +/- 3.0 V
Grid sell frequency range on AC1 59.4 to 60.4 +/- 0.05 Hz 59.4 to 60.4 +/- 0.05 Hz
(auto adjust entering sell mode)
Efficiency
Peak 95.7% 95.7%
CEC weighted efficiency 93.0% 92.5%
General specifications
Part number 865-5548-01 865-6848-01
Product / shipping weight 53.5 kg (118.0 lb) / 75.0 kg (165.0 lb) 55.2 kg (121.7 lb) / 76.7 kg (169.0 lb)
Product dimensions (H x W x D) 58 x 41 x 23 cm (23 x 16 x 9 in) 58 x 41 x 23 cm (23 x 16 x 9 in)
Shipping dimensions (H x W x D) 71.1 x 57.2 x 39.4 cm (28.0 x 22.5 x 15.5 in) 71.1 x 57.2 x 39.4 cm (28.0 x 22.5 x 15.5 in)
IP degree of protection NEMA Type 1 Indoor
Operating air temperature range -25°C to 70°C (-13°F to 158°F) (power derated above 25°C (77°F)
Warranty (Depending on the country of installation) 2 or 5 years 2 or 5 years
Features
System monitoring and network communications Available
Intelligent features Grid sell, peak load shave, generator support, prioritized consumption of battery or external DC energy
Auxiliary port 0 to 12 V, maximum 250 mA DC output, selectable triggers
Off-grid AC coupling Frequency control
Regulatory approval
Safety UL1741, CSA 107.1
EMC directive FCC and Industry Canada Class B
Interconnect IEEE 1547 and CSA 107.1
Compatible products
Conext XW+ Power Distribution Panel 865-1014-01
Conext System Control Panel 865-1050
Conext Automatic Generator Start 865-1060
Conext MPPT 60 150 865-1030-1
Conext MPPT 80 600 865-1032
Conext ComBox 865-1058
Conext Battery Monitor 865-1080-01
Conext Battery Fuse Combiner Box 865-1031-01
Conext Portable Installation and Configuration Tool Product no. 865-1155-01
Specications are subject to change without notice.