Faults and Warnings
When a fault or warning message appears on the Conext Gateway device status page,
you can acknowledge the message to clear the screen. To acknowledge a fault or
warning message, press the Enter button. This action does not clear the fault or warning
condition - consult Table 23 on page 110 and Table 26 on page 115 for suggested actions
after you have acknowledged the message.
Warning Messages
Warning messages appear on the Conext Gateway to alert you to an impending system
change. You can access all past warnings for a device in the Conext Gateway web
application by navigating to Events > Historical Events in the Conext XW Pro
status page. Each warning has a time stamp to let you know the date and time that the
warning appeared.
If several warning messages occur before you can acknowledge or clear them, they are
displayed together on a warning list. This list contains messages from every Xanbus-
enabled device, not just the Conext XW Pro. You can select a message and view its
details from warning list.
Warning Types
There are two types of warnings: automatic and manual. When the Conext XW Pro
detects a warning condition, it displays a warning message on the Conext Gateway web
application. Table 22 describes how their behavior differs and how you can respond to
them.
Warning type Behavior
Automatic
warning
Clear automatically if the warning condition that generated the message
goes away. You can also acknowledge automatic warnings without
waiting for them to clear automatically.
Manual warning
Require you to clear them manually via the Conext Gateway web
application before you can proceed with configuring or operating the
Conext XW Pro.
Table 22Warning Types and Behavior
Table 23 provides descriptions of the warning messages and solutions.
Warning
Number
Message Name
Warning
Type
Cause Solution
W44
Battery Over
Temperature
Automatic Battery Over Temperature
Warning. Battery temperature is
over 50 °C (122 °F).
Check battery voltage and battery
cable connections. Stop charging, if
necessary. Check for excessive
ambient temperature and adequate
ventilation in the battery compartment
Table 23Warning Messages
Conext XW Pro Owner's Guide Troubleshooting
110 This document is intended for use by qualified personnel 990-91227A-01