Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Warning
Number
Message Name
Warning
Type
Cause Solution
W64
AC Overload Automatic See W63. See W63.
W68
Transformer Over
Temperature
Automatic See W57. See W57.
W90
BMS Status Lost Automatic BMS Status from the Conext
Gateway is not being received.
Verify connectivity between BMS,
Conext Gateway, and Conext XW Pro.
Verify Battery Type and Charge Cycle
settings appropriate for the
application.
W92
Conext Gateway
Comms Lost
Automatic Conext XW Pro has lost
communication with the Conext
Gateway.
Verify connectivity with Conext
Gateway.
W93
SunSpec Controller
Comms Lost
Automatic Conext XW Pro has lost
communication with the
SunSpec Controller.
Verify connectivity of Conext Gateway
with SunSpec Controller.
If no SunSpec Controller exists on the
network, refer to the Conext Gateway
Owner’s Guide (975-0806-01-03).
W94
Remote Power Off Automatic The unit has been turned off
with a Remote Power Off
switch.
No action required. The unit stops
inverting or charging immediately, and
shuts down after five seconds. If the
unit is configured as a master, it
signals other network devices to also
shut down.
W95
Equalize Abort Manual Equalization terminated
abnormally because of
interrupted AC input.
Wait until AC input (utility grid) returns
to in-tolerance condition.
W96
Cannot Equalize Manual The selected battery type
should not be equalized.
Change battery type if your batteries
should be equalized. Gel or AGM
batteries should not be equalized.
AC input is not qualified or the
charge setting is not adequate.
Check for presence of AC. Make sure
Charge and Equalize are enabled.
Verify the Conext AGS trigger is set to
Stop Float. If Stop Voltage is
enabled, then the voltage level should
be above the Equalize Voltage
Setpoint level.
W97
Battery temperature
sensor failure
Automatic Battery Temperature Sensor
Shorted
Replace battery temperature sensor.
W500
Lost network
connection
Automatic Lost network connection Check network cables.
Conext XW Pro Owner's Guide Troubleshooting
112 This document is intended for use by qualified personnel 990-91227A-01