Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Specification XW Pro 6848 NA
Surge Current (Inverter Mode)
52 A
RMS
for 60 seconds (240 V
nominal)
AC Input Voltage Range (Bypass/Charger Mode) 160-270 VAC (240 V nominal)
AC Input Frequency Range (Bypass/Charger Mode)
52-68 Hz (default) 44-70 Hz
(allowable)
AC Input Maximum Breaker Capacity 60 A maximum, double-pole
AC Output Maximum Breaker Capacity 60 A maximum, double-pole
AC1 (Grid) Input Current 3 - 60 A
AC2 (Generator) Input Current 3 - 60 A
AC Output Frequency 60.0 ± 0.1 Hz
Total Harmonic Distortion < 5% at rated power
Automatic Transfer Relay Capacity & Typical Transfer
Time
60 A / 8 ms
Auxiliary Relay Output 0 - 12 VDC, Maximum 250 mA
Grid Sell Current (Selectable Limit) 0 - 27 A
RMS
(240 V nominal)
Grid Sell Power 6,000 W
Peak Efficiency 95.1%
CEC Weighted Efficiency 93.0%
Mechanical Specifications
NOTE: Specifications are subject to change without prior notice.
Model XW Pro 6848 NA
Non-Volatile Memory Yes
Inverter Information Panel
Status LEDs indicate AC In status,
events/warnings, equalize mode,
battery level. 3-character display
indicates output power or charge
current, event/warning codes.
STARTUP/SHUTDOWN and equalize
button
Multiple Unit Configurations
Up to 3 parallel units in 120/240
three-wire configuration.
Electrically, up to 4 parallel units
can be connected and operated.
Table 28Conext XW Pro Mechanical Specifications
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 123