Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
P(V) Volt-Watt Function
When the Conext XW Pro is in Grid Support mode and P(V) function is enabled:
n The Conext XW Pro dynamically increases the active power injected into the utility
grid from the pre-disturbance level when AC voltage trends lower than V2, following
the P1P2 segment in the figure below.
n The Conext XW Pro dynamically curtails active power injected into the utility grid
from the pre-disturbance level when AC voltage trends higher than V5, following
P5P6 segment in the figure below.
n By adjusting the active power in response to grid voltage fluctuations, Conext XW
Pro contributes to grid stabilization towards the nominal value.
The P(V) function is enabled by default.
Figure 35P(V) Volt-Watt Function
P The Conext XW Pro output active power in percentage of nominal rated active power
Pn.
V - Utility grid voltage in percentage) of nominal voltage Vn [%Vn]
For example, V1 = 90% means V1=216 V for Vn = 240 V nominal grid.
Parameter
Voltage [% Vn] Active Power [%Pn]
Default Range Default Range
Point P1 90 85 to 99 100 0 to 100
Point P2 94 90 to 99 0 0
Point P3 95 90 to 100 0 0
Point P4 105 100 to 110 0 0
Point P5 106 101 to 110 0 0
Point P6 110 101 to 115 -100 -100 to 0
Table 31Rule 21 P(V) Volt-Watt function default and adjustability range
settings
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 133