HVRT
Time [s] Voltage [%Vn]
Default Range Default Range
Point P1.H 0.16 N/A 120 115 to 125
Point P2.H 13 1 to 13 120 115 to 125
Point P3.H 13 1 to 13 110 100 to 115
Table 33Rule 21 High Voltage Ride-through (HVRT) default and adjustability range
settings
LVRT
Time [s] Voltage [%Vn]
Default Range Default Range
Point P1.L 1.5 0.16 to 1.5 50 0 to 50
Point P2.L 11 1 to 11 50 0 to 50
Point P3.L 11 1 to 11 70 50 to 80
Point P4.L 21 2 to 21 70 50 to 80
Point P5.L 21 2 to 21 88 80 to 100
Table 34Rule 21 Low Voltage Ride-through (LVRT) default and adjustability range
settings
Frequency Ride-Through (FRT)
The Conext XW Pro has the capability of remaining connected to the utility grid and
operational for defined time intervals (ride-through) while AC frequency deviates from
nominal range, as seen in the figure below.
n At the end of ride-through time, if the utility grid frequency has not recovered to the
near nominal (NN) range, the Conext XW Pro will disconnect and transition to Inverter
(Grid-Forming) Mode.
Frequency Ride-through is enabled by default.
Figure 38High/Low Frequency Ride-through (HFRT/LFRT) regions
n When in Continuous Operation region (Near Nominal), Conext XW Pro operates
indefinitely without tripping.
n When in Low-Frequency 1 (LF2) or High-Frequency 2 (HV2) regions, Conext XW Pro
Conext XW Pro Owner's Guide Specifications