goes into Momentary Cessation (i.e. stop injecting output current to utility grid; it does
not imply galvanic isolation or disconnection).
n When in Low-Frequency 1 (LF1) orand High-Frequency 1 (HF1), Conext XW Pro goes
into Mandatory Operation (i.e. generates an output current greater than or equal to
80% of pre-disturbance current value).
HFRT
Time [s] Frequency [Hz]
Default Range Default Range
Point P1.H 0.16 0.16 to 10 62 62 to 64
Point P2.H 300 2 to 300 62 62 to 64
Point P3.H 300 2 to 300 60.5 60.1 to 62
Table 35Rule 21 High Frequency Ride-through (HFRT) default and adjustability range
settings
LFRT
Time [s] Frequency [Hz]
Default Range Default Range
Point P1.L 0.16 0.16 to 10 57 53 to 57
Point P2.L 300 2 to 300 57 53 to 57
Point P3.L 300 2 to 300 58.5 57 to 59.9
Table 36Rule 21 Low Frequency Ride-through (LFRT) default and adjustability range
settings
Specifications Conext XW Pro Owner's Guide
990-91227A-01 This document is intended for use by qualified personnel 137