Conext XW PRO 6848 6,800W 48V Installation

Table Of Contents
Ramp Rates
Normal Ramp Rate
During normal operation, any transition between power output levels will be executed at a
ramp rate no larger that the Normal Ramp Rate setting. Normal Ramp Rate is contingent
upon sufficient energy available at the Conext XW Pro DC input port.
Normal Ramp Rate function is enabled by default.
Figure 39Normal ramp rate
n Normal Ramp rate is defined as a slope measured in percentage of AC nominal
current per second [%In/sec].
n Default Normal Ramp Rate value is 100 [%In/sec] with an adjustability range from 1
to 100 [%In/sec].
Parameter
AC Current per second [%In/s]
Default Range
Ramp Rate 100 1 to 100
Parameter
Time [s] AC Current [%In]
Default Range Default Range
Point P1 0 N/A 0 N/A
Point P2 1 N/A 100 N/A
Conext XW Pro Owner's Guide Specifications