Reconnection (Soft-Start) Ramp Rate
Upon starting up, returning to service, or re-connecting, the Conext XW Pro limits the
rate of exported/generated active power to no larger that the Ramp Rate setting.
Normal Ramp Rate function is enabled by default.
Figure 40Reconnection ramp rate
n Normal Ramp rate is defined as a slope measured in percentage of AC nominal
current per second [%In/sec].
n The default Normal Ramp Rate value is 2 [%In/sec] with an adjustability range from 1
to 100 [%In/sec].
Parameter
AC Current per second [%In/s]
Default Range
Ramp Rate 2 N/A
Parameter
Time [s] AC Current [%In]
Default Range Default Range
Point P1 0 N/A 0 N/A
Point P2 50 1 to 100 100 N/A