Grid Disconnect Settings
The Conext XW Pro will remain connected to the utility grid as long as voltage and
frequency are within the qualified range (i.e. less than the Over Voltage/Frequency limit
and higher than the Under Voltage/Frequency limit).
California Rule 21 implements voltage and frequency disconnect limits via High/Low
Voltage Ride Through (H/LVRT) and via High/Low Frequency Ride Through (H/LFRT)
curves.
Grid voltage and frequency disconnect settings are defined in the table below, and take
effect only when the H/LVRT and H/LFRT curves are disabled.
Anti-Islanding
Disconnect
Slow Delay
The disconnection time delay for the grid voltage exceeding an over-
voltage voltage level, but lower than the fast disconnection level. The
default value for this setting is 0.5 seconds.
Anti-Islanding
Disconnect
Over
Frequency
The frequency above which the Conext XW Pro will stop export of power
and record an islanding fault. The default value for this setting is 62Hz.
The disconnect will occur if the inverter is over frequency for 0.1 seconds.
Anti-Islanding
Disconnect
Under
Frequency
The frequency below which the Conext XW Pro will stop export of power
and record an islanding fault. The default value for this setting is 57 Hz,
and the disconnect will occur if the inverter is under frequency for 0.1
seconds.
Anti-Islanding
Disconnect
Over Voltage L-
N Fast
The line-to-neutral voltage above which the Conext XW Pro will stop
export of power and record an islanding fault. The default value for this
setting is 144 V.
Anti-Islanding
Disconnect
Over Voltage L-
N Slow
The line-to-neutral voltage above which the Conext XW Pro will stop
export of power and record an islanding fault. The default value for this
setting is 132 V, and the disconnect will occur if the inverter is over
frequency for 0.5 seconds.
Anti-Islanding
Disconnect
Over Voltage
L1-L2 Fast
The line-to-line voltage above which the Conext XW Pro will stop export of
power and record an islanding fault. The default value for this setting is
288 V.
Anti-Islanding
Disconnect
Over Voltage
L1-L2 Slow
The line-to-line voltage above which the Conext XW Pro will stop export of
power and record an islanding fault. The default value for this setting is
264 V, and the disconnect will occur if the inverter is over voltage for 0.5
seconds.
Anti-Islanding
Disconnect
Under Voltage
L-N Fast
The line-to-neutral voltage below which the Conext XW Pro will stop
export of power and record an islanding fault. The default value for this
setting is 60 V.
Table 37Rule 21 Grid Disconnect Settings
Conext XW Pro Owner's Guide Specifications